10 Troubleshooting
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
10-
2 T
rou
blesh
oo
tin
g
10
The RUN command
is input, but the
motor does not
rotate.
The RUN Direction Limit Selec-
tion (b035) is set to limit the for-
ward or reverse rotation.
Set the RUN Direction Limit Selection (b035)
correctly.
P. 7-38
The input terminal wiring or
short-circuit bar connection for
the RUN command is incorrect.
Wire correctly. (The multi-function input termi-
nal status can be checked in the Multi-func-
tion Input Monitor (d005).)
P. 2-10
P. 2-12
P. 2-33
The analog voltage/current or
variable resistor input wiring for
the frequency reference is
incorrect.
Wire correctly.
• For the analog voltage or variable resistor
input wiring, measure the voltage between
the terminals FC and SC with a tester etc.
to check that the voltage is correct.
• For the analog current input wiring, with the
wires disconnected, measure the current
flowing between the power supply and FI
terminals with a tester etc. to check that the
current is correct.
P. 2-10
P. 7-22
Although the inverter is oper-
ated via the Digital Operator,
the Multi-function Input S1 to
S7 Selection (C001 to C007) is
set to 51 (F-TM: Forced termi-
nal block) and that terminal is
ON.
Turn OFF the terminal to which the function is
allocated.
P. 7-55
Although the inverter is oper-
ated via the control circuit termi-
nal block, the Multi-function
Input S1 to S7 Selection (C001
to C007) is set to 31 (OPE:
Forced operator function) and
that terminal is ON.
Turn OFF the terminal to which the function is
allocated.
P. 7-55
The inverter trip occurred. (The
ALARM LED is lit with “Exxx”
on the display.)
Press the STOP/RESET key to reset the trip
and, after determining the cause and taking
countermeasures based on the alarm code,
restart the inverter.
P. 5-43
P. 10-2
When the safety function selec-
tor switch is ON, either the
multi-function input terminal
S3/GS1 or S4/GS2 is OFF.
To use the safety function, turn ON both of the
safety input terminals GS1 and GS2. To dis-
able this function, set the safety function
selector switch to OFF.
P. 7-97
The Multi-function Input S1 to
S7 Selection (C001 to C007) is
set to 18 (RS: Reset), 14 (CS:
Commercial switching), or 11
(FRS: Free-run stop) and that
terminal is ON.
Turn OFF the terminal to which the function is
allocated.
P. 5-39
P. 5-53
P. 7-50
The Multi-function Input S1 to
S7 Selection (C001 to C007) is
set to 84 (ROK: Permission of
RUN command) and that termi-
nal is ON.
Turn ON the terminal to which the function is
allocated.
P. 7-38
The wiring from the inverter to
the motor, or the internal wiring
of the motor, is disconnected.
Check the input wiring.
P. 2-10
P. 2-28
The load is too heavy.
Reduce the load.
−
The motor brake is applied.
Release the brake.
−
Symptom
Possible cause
Remedy
Reference
page
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...