7 Other Functions
7 - 22
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-3
Analog I/O Settings
This section describes the analog I/O signal settings for this inverter.
This inverter has two types of external analog input terminals.
For analog input start/end settings, refer to
7-3-5 Analog Input Start/End Function Settings
on page 7-25.
Note
By default, each analog input signal is adjusted to reach the maximum frequency at 9.8 V or 19.8 mA.
The table below shows analog-input related functions. Set each function according to your application.
7-3-1
Analog Input (FV, FI)
Frequency reference (Analog voltage input) between terminals FV and SC
: 0 to 10 V
This terminal also treats input via the variable resistor (volume) as voltage input to the
inverter.
Frequency reference (Analog current input) between terminals FI and SC
: 4 to 20 mA
For 0 to 20 mA, set A103 to 0%.
Parameter
No.
Setting item
Function name
Data
Default
data
Unit
A001/A201
Frequency
reference
*1
1st/2nd Frequency
Reference Selection
01:
Control circuit terminal
block
(Analog input)
02
−
A071
PID feedback
selection
*2
PID Selection
01:
Enabled
00
−
02:
Enabled (Reverse out-
put enabled)
A076
PID Feedback
Selection
00:
FI (Current)
00
−
01:
FV (Voltage)
A071
PID feedforward
selection
*3
PID Selection
01:
Enabled
00
−
02:
Enabled (Reverse out-
put enabled)
A079
PID Feedforward
Selection
01:
FV (Voltage)
00
−
02:
FI (Current)
A001/A201
Calculation
frequency
1st/2nd Frequency
Reference Selection
10:
Operation function
output
02
−
A141
Calculation Frequency
Selection 1
02:
Input FV (Voltage)
02
−
A142
Calculation Frequency
Selection 2
03:
Input FI (Current)
03
−
A143
Calculation Function
Operator Selection
00:
Addition (A141
+
A142)
00
−
01:
Subtraction (A141
−
A142)
02:
Multiplication (A141
×
A142)
b040
Torque limit
*4
Torque Limit Selection
02:
Analog voltage input
00
−
P033
Torque control
Torque Reference
Input Selection
00:
Terminal FV
10 V = 200%
00
−
01:
Terminal FI
20 mA = 200%
C001 to
C007
Multi-function Input S1
to S7 Selection
52:
ATR
(Torque reference input
permission)
−
−
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...