8 - 7
8 Communications Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
8
-4 Mo
dbu
s Co
mm
uni
catio
n Prot
ocol
8
8-4
-1 Messa
ge Configura
tion
8-4
Modbus Communication Protocol
The inverter communicates with external controllers as follows.
(1) Frame (Query) that is sent from the external control device to the inverter
(2) After receiving a query frame, the inverter waits the total time of the silent Interval
and the Communication Wait Time (C078), before returning a response.
Silent interval
The wait time that is specified on Modbus communication; its data length is 3.5 characters
(3.5 bytes).
It depends on the Modbus communication speed setting.
(3) Frame (Response) that is sent from the inverter back to the external controller.
(4) After sending a response, the inverter monitors the time until it completes receiving
the query frame from the external control device. The inverter judges it as a commu-
nications error if it receives no response within the Communication Error Timeout
Time (C077).
Then, the inverter operates according the Operation Selection on Communication Error
(C076), while waiting for the reception of the first data again.
The monitoring of the Communication Error Timeout Time starts from the first send-
ing/receiving operation is established after the power supply is cycled or after the inverter is
reset.
The inverter does not recognize as a communications error timeout if the sending/receiving
operation is not established at all.
The command message sent from the master to a slave (or slaves) is called “query” and the response
message returned from the slave(s) is called “response.” The transmission format of a query/response
is as follows.
(Example) 1 character:10 bits (1 start bit
+
8 data bits
+
1 stop bit)
Time required per character: 1/9,600 (bps)
×
10 (bit)
×
1,000 = 1.04 ms
Time required for 3.5 characters: 1.04 ms
×
3.5 = 3.64 ms
However, according to the Modbus specifications, this time is fixed to 1.75 ms
for communications speeds exceeding 19.2 kbps.
8-4-1
Message Configuration
Query
Response
Slave address
Confirmation slave address
Function code
Confirmation function code
Query data
Response data
Error check (CRC-16)
Error check (CRC-16)
External
controller
Inverter
(2) Wait time
(Silent Interval
+
C078)
(4) Communication Error
Timeout Time (C077)
(1) Query
(3)
Response
Time
(1) Query
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...