7 - 35
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-
5 O
the
r O
p
era
tion
Fu
nct
ion
s
7
7-5
-1 S
tarting F
requency
7-5
Other Operation Functions
This section describes the parameters associated with other operation functions.
Set the frequency at which the inverter starts its output when the RUN signal turns ON.
Mainly, use this function to adjust the starting torque.
If you set a high frequency in Starting Frequency (b082), the inverter starts with the full voltage and also
the starting current increases. Therefore, the overload limit function may be performed or the inverter
may trip easily by the overcurrent protection.
7-5-1
Starting Frequency
Parameter No.
Function name
Data
Default
data
Unit
b082
Starting Frequency
0.01 to 9.99
1.50
*1
*1. The default data was changed from the previous model.
Hz
b082
RUN command
(FW input)
Output frequency
Output voltage
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...