6 - 11
6 Vector Control and Applied Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
6-1 Sen
sorless V
ect
or Co
ntro
l
6
6-
1-4 Adjustment
s for Sensorless V
ector Co
ntrol
This function is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless
vector control).
When sensorless vector control is enabled, the inverter may output a rotation signal opposite to the
RUN command direction at low speeds, depending on the current accuracy. To prevent the motor from
rotating in the reverse direction, set the Reverse Rotation Prevention Selection (b046) to 01 (Enabled).
Use this function to monitor the motor output torque estimated by the sensorless vector control func-
tion.
This function is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless
vector control).
To monitor the motor output torque via the Digital Operator, display the Output Torque Monitor (d012).
For details on Output Torque Monitor, refer to
7-1-11 Output Torque Monitor [d012]
on page 7-8.
For how to monitor the motor output torque via the control terminal block signal, refer to
7-3-6 Terminal
MP (Pulse/PWM Output)
on page 7-27 or
7-3-7 Terminal AM (Analog Output)
on page 7-29.
The output torque monitor function estimates the torque value equivalent to the rated current of the
inverter as 100%.
To convert it to the rated motor torque ratio, use the following formula:
Reverse Rotation Prevention Function
Parameter No.
Function name
Data
Default data
Unit
b046
Reverse Rotation
Prevention Selection
00:
Disabled
00
−
01:
Enabled (Motor does not rotate in
reverse.)
Output Torque Monitor Function (d012)
Rated motor torque ratio = [Output Torque Monitor (d012) value]
×
[Rated output current of inverter]
/ [Rated motor current]
Parameter No.
Function name
Data
Default data
Unit
A044/A244
1st/2nd Control Method
03:
Sensorless vector control
00
−
d012
Output Torque Monitor
−
200. to 200.
−
%
C027
C028
MP Selection
AM Selection
02:
Output torque
07
−
11:
Output torque (signed)
*1
*1. This setting is available for C028 only.
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...