10 - 7
10 Troubleshooting
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
10-
1 Alarm
Displ
ay and
Rem
e-
di
es
10
1
0-1-2
Alar
m Code List
Name
Description
Alarm
code
Check and remedy
Reference
page
Driver error
*1
*1. If this error occurs, the inverter will not accept the reset operation via the terminal RS or the STOP/RESET key.
Turn off the power supply once.
If this error is still displayed at the next power-on, it is possible that the memory is corrupt or the parameters
are not stored correctly. Perform parameter initialization to reset the parameter settings.
This error is detected by the driver IC
incorporated in the inverter.
The inverter trips to protect the main
element if a momentary overcurrent
(approximately 350% or higher of the
rated current), abnormal temperature
in the main element, or drop of the
main element drive power supply
occurs. (If this trip occurs, the inverter
cannot be restarted.)
E30.
Is there any output short-circuit?
• Check the output wiring.
Is there any ground fault?
• Check the output wiring and
the motor.
Is the main element damaged?
• Check the IGBT. For the
check method, refer to
11-1-7
Inverter/Converter Unit Test
on page 11-7.
Is the cooling fin clogged?
• Clean the fin.
P. 11-8
Thermistor
error
The inverter trips if it detects an
abnormal temperature from the resis-
tance value of an external thermistor
when the thermistor input function is
enabled.
E35.
Is the motor temperature too
high?
• Check the temperature.
Is the thermistor damaged?
• Check the thermistor.
Is there any noise in the thermis-
tor signal?
• Separate the wiring.
P. 7-80
Brake error
The inverter trips if it cannot recognize
the ON/OFF status of the brake within
the Brake Error Detection Time
(b124) after outputting the brake
release signal, when the brake control
function is enabled (b120 = 01).
E36.
Is the brake ON/OFF function
working?
• Check the brake.
Is the time set in b124 too short?
• Increase the b124 value.
Is the brake confirmation signal
input?
• Check the wiring.
P. 6-25
P. 6-49
Emergency
shutoff
*2
*2. In this case, the trip cannot be reset using the STOP/RESET key. Cycle the power supply or perform the reset
operation via the terminal RS (Reset) to reset the trip.
The inverter trips if the safety input
terminal GS1/GS2 are input.
E37.
Are the GS1/GS2 signals input to
the terminal correctly?
• Check the wiring and
sequence.
Is the parameter set correctly?
• Check the GS Input Opera-
tion Selection (b145) setting.
P. 7-98
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...