7 - 23
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-3 A
n
alo
g
I/O Setting
s
7
7-3
-1 Analog Input (
F
V
, FI)
When the analog input is used as a frequency reference, switching between voltage (FV) and current
(FI is performed) is performed as shown in the table below.
However, when none of the multi-function input terminals are set to 16 (AT: Analog input switching),
regardless of the A005 setting, the frequency reference value is the sum of the analog voltage input FV
and analog current input FI values.
Note
For details on frequency reference settings, refer to
5-5 Frequency Reference Settings
on page 5-24.
*1. This switches the frequency reference among the volume, current, and voltage based on the FV/FI Selection
(A005) setting and the status of the multi-function input terminal allocated to 16 (AT: Analog input switching).
Here, volume represents the volume control (VR) on the optional Digital Operator (Model: 3G3AX-OP01).
*2. Setting the PID Selection (A071) to Enabled causes the analog input selection setting in A076 to be allocated
to the PID feedback function. When the 1st Frequency Reference Selection (A001) is set to 01 (Control circuit
terminal block), the analog input setting other than that selected in A076 is used as the target frequency refer-
ence. In this case, the setting in A005 and the function allocated to the terminal AT (Analog input switching)
are disabled.
*3. In A079, you can set a target value, or have a setting that overlaps with the PID Feedback Selection value.
With an overlapping setting, the analog input is used for both the feedback and feedforward signals.
*4. This parameter can be set to 02 (Analog voltage input) only. The torque limit is 200% with an input of 10 V.
Parameter
No.
Function
name
Data
Default
data
Unit
A005
FV/FI
Selection
00:
Switches between current and voltage based on ter-
minal AT (Analog input switching) status.
00
−
Terminal AT (Analog input switching) ON:
Current
Terminal AT (Analog input switching) OFF: Voltage
02:
Enabled only when 3G3AX-OP01 is used.
Switches between voltage and VR based on terminal
AT (Analog input switching) status.
Terminal AT (Analog input switching) ON:
VR
Terminal AT (Analog input switching) OFF: Voltage
03:
Enabled only when 3G3AX-OP01 is used.
Switches between current and VR based on terminal
AT (Analog input switching) status.
Terminal AT (Analog input switching) ON:
VR
Terminal AT (Analog input switching) OFF: Current
C001 to
C007
Multi-function
Input S1 to S7
Selection
16:
AT (Analog input switching)
−
−
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...