This signal will be output when the output current falls to or below the Low Current Detection Level
(C039).
In the Low Current Signal Output Selection (C038), select whether to have the inverter output this sig-
nal constantly during run or only during constant speed operation.
If any of the following trips occurs, the inverter will output a separate signal besides the alarm signal
(05: AL).
This signal indicates that the trip is associated with a hardware failure.
7-8-18 Low Current Signal (LOC)
Parameter
No.
Function name
Data
Default
data
Unit
C038
Low Current Signal Output Selection
00:
Enabled during accelera-
tion/deceleration and
constant speed
01
−
01:
Enabled during constant
speed
*1
*1. When the 1st/2nd Frequency Reference Selection (A001/A201) is set to 01 (Control circuit terminal block (An-
alog input)), the signal may not be judged as a constant speed depending on the sampling condition. In this
case, set C038 to 00 (Enabled during acceleration/deceleration and constant speed) or increase the value set
in the Analog Input Filter (A016).
C039
Low Current Detection Level
0.00 to 2.00
×
Rated current
(In the heavy mode)
0.00 to 1.50
×
Rated current
(In the light mode)
Set the output level of the low
current signal.
Rated
current
A
C021, C022
Multi-function Output P1/P2 Selection 43:
LOC (Low current signal)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
7-8-19 Fatal Fault Signal (MJA)
Alarm code
Description
E08.
EEPROM error
E10.
Current detector error
E11.
CPU error
E14.
Ground protection
E22.
CPU communications error
E25.
Main circuit error
Parameter
No.
Function name
Data
Default
data
Unit
C021, C022
Multi-function Output P1/P2 Selection 53:
MJA (Fatal fault signal)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
ON
ON
Output current [A]
Low current (LOC) output
Low Current Detection
Level (C039)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...