2 - 45
2 Design
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
2-3
W
irin
g
2
2-
3-9 C
ompliance with EC Directives
z
EMC noise filters
OMRON is currently preparing a line up of EMC noise filters.
z
Wiring for power supply
Keep the ground cable as short as possible.
Place the inverter and the noise filter on the same earth (ground) plate.
Always connect the power supply input terminals (R/L1, S/L2, T/L3) of the inverter to the power sup-
ply via an EMC noise filter.
Keep the cable between the inverter and the EMC noise filter as short as possible (40 cm maximum).
Connection Example
z
Wiring between inverter and motor
For cables between the inverter and motor, be sure to use shield braided cables.
Keep the cables as short as possible.
z
Measures against noise for compliance with EMC Directive
• Keep the power cable of the inverter and the EMC noise filter wiring as short as possible.
Use a shield braided cable.
• For the shield braided cable, use a tinned copper shielded cable with a shield factor of 85%.
• Be sure to connect the ground cable separately from the shielded cable. Use the ground cable as
thick and short as possible to wire.
• Use shield braided cables for connection between the inverter and the motor. Keep the cables as
short as possible at a length 20 m or less, with the cable shield grounded at each end. Installing a
clamp filter near the inverter output terminals is an effective countermeasure.
• Ground the motor frame, the shield of the motor cable, and the terminal housing adequately.
• The motor terminal housing may not contact with the chassis due to the rubber bushing or the
screw hole for motor ground terminal may be coated. Check the contact performance. If there is
any problem, take measures to enhance contact performance.
• Use shielded cables for wiring to the control circuit terminals and communications lines and
ground the shield of each cable on the inverter side. Grounding the cables at each end may
increase the effect.
• Connect the cable shield directly to a ground plate with a conductive cable clamp. At this time,
keep the shield strip length as short as possible.
• Make the contact area between the EMC noise filter/Inverter and the ground plate as large as
possible to enhance contact performance. At this time, remove the paint etc. from the ground
plate.
• For the control panel door, use a conductive gasket to improve the shielding effect.
• In the same control panel, do not install equipment that generates non-EMC-compliant electro-
magnetic waves.
• Avoid conductor loops that encompass large areas.
L1
L2
L3
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
M
(Power
supply)
L1' (Red)
EMC
noise filter
Inverter
Molded case
circuit breaker
Motor
L2' (White)
L3' (Blue)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...