7 - 83
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-
8 Fu
nct
ion
s Relat
ed to
Prot
ectio
n, W
arnin
g, an
d V
ariou
s O
u
tp
ut
Si
gnal
s
7
7-8
-1
1 Lo
gic Operation Output Signal (LOG1 to LOG3)
Use these signals to have the inverter internally perform logical operations with output signals. Set the
Multi-function Output P1/P2 Selection (C021/C022), or Multi-function Relay Output (MA, MB) Function
Selection (C026), to 33 (LOG1: Logic operation output 1), 34 (LOG2: Logic operation output 2), or 35
(LOG3: Logic operation output 3). The logic output signal selection parameters cannot be set to 255
(no: No allocation), 63 (OPO: Option), or 33 to 35 (LOG1 to LOG3: Logic operation output 1 to 3).
Three operators, AND, OR, and XOR, are available.
Each logic operation output signal requires different parameter settings.
Set the necessary parameters according to the table below.
7-8-11 Logic Operation Output Signal (LOG1 to LOG3)
Selected signal
Logic output sig-
nal selection 1
Logic output sig-
nal selection 2
Operator selec-
tion
33:
Logic operation output 1 (LOG1)
C142
C143
C144
34:
Logic operation output 2 (LOG2)
C145
C146
C147
35:
Logic operation output 3 (LOG3)
C148
C149
C150
(Example) To output the result of the AND operation between RUN (00: Signal during RUN) and FA2
(01: Set frequency exceeded signal) to the multi-function output terminal P2 as a logic oper-
ation output 1 (LOG1) terminal
Multi-function Output P2 Selection (C022)
: 33 (LOG1)
Logic Output Signal 1 Selection 1 (C142)
: 00 (RUN)
Logic Output Signal 1 Selection 2 (C143)
: 02 (FA2)
Logic Output Signal 1 Operator Selection (C144) : 00 (AND)
Parameter
No.
Function name
Data
Default
data
Unit
C142
C145
C148
Logic Output Signal 1 to 3
Selection 1
00 to 63: Same as options for C021
(Except 33 (LOG1) to 35 (LOG3), 63
(OPO), and 255 (no))
00
−
C143
C146
C149
Logic Output Signal 1 to 3
Selection 2
00
−
C144
C147
C150
Logic Output Signal 1 to 3
Operator Selection
00:
AND
00
−
01:
OR
02:
XOR
Logic output sig-
nal selection 1
LOGx (AND)
LOGx (XOR)
Logic output sig-
nal selection 2
LOGx (OR)
RUN
LOG1
FA2
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...