6 Vector Control and Applied Functions
6 - 8
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5
Operations in case of error
If auto-tuning is aborted due to an error, review the preset parameters according to “1. Preset-
ting of parameters” and check that the rated torque of the motor is at least 50% of the rated out-
put current of the inverter. If the load is too heavy, disconnect it and retry auto-tuning.
If the error persists or auto-tuning is still aborted, enter the motor parameter values directly.
For details, refer to
6-1-3 Motor Parameter Settings
on page 6-9.
Precautions for Correct Use
• If a trip occurs during auto-tuning, the auto-tuning process will be force-terminated and the
inverter displays a trip. In this case, refer to
10-1-2 Alarm Code List
on page 10-4.
• If the auto-tuning process is not ended, press the STOP/RESET key or reset the RUN com-
mand. This causes the process to be forcibly ended. In this case, the auto-tuning result will
not be displayed. Then, review the preset parameters in “1. Presetting of parameters”.
• If the rated current of the motor is 50% of the rated output current of the inverter or lower,
auto-tuning may not work.
The inverter may not provide sufficient performance characteristics due to the current accu-
racy if your motor is two or more sizes lower than the maximum applicable motor capacity.
• If the auto-tuning process is aborted, or if you interrupt the process by pressing the
STOP/RESET key or by resetting the RUN command, the auto-tuning settings may be left in
the parameters H030/H230 to H034/H234.
Parameter No.
Function name
Data
Default data
Unit
H002/H202
1st/2nd Motor Parameter
Selection
00: Standard motor parameter
00
−
02: Auto-tuning parameter (Applies
H030/H230 to H034/H234 data to motor
parameters.)
H030/H230
1st/2nd Motor Parameter
R1 (Auto-tuning Data)
0.001 to 9.999
10.00 to 65.53
Dependent
on motor
capacity
Ω
H031/H231
1st/2nd Motor Parameter
R2 (Auto-tuning Data)
H032/H232
1st/2nd Motor Parameter
L (Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
mH
H033/H233
1st/2nd Motor Parameter
lo (Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
A
H034/H234
1st/2nd Motor Parameter
J (Auto-tuning Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
kgm
2
A045/A245
1st/2nd Output Voltage
Gain
20. to 100.
100.
%
A051
DC Injection Braking
Selection
00: Disabled
00
−
01: Enabled
02: Enabled (Operates only at set frequency)
P012
Simple Position Control
Selection
00: Simple position control disabled
00
−
02: Simple position control enabled
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...