7 Other Functions
7 - 38
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Use this function to limit the RUN direction of the motor.
It can be activated either via the control circuit terminal block or the Digital Operator.
When the inverter receives a RUN command input with the RUN direction limit function enabled from
the control circuit terminal block,
is displayed on the Digital Operator.
Use this function to have the inverter accept the RUN command only while the permission of RUN com-
mand is ON.
To use it, set the Multi-function Input S1 to S7 Selection (C001 to C007) to 84 (ROK).
7-5-5
RUN Direction Limit Selection
Parameter
No.
Function name
Data
Default
data
Unit
b035
RUN Direction Limit
Selection
00:
No direction limit
00
−
01:
Only Forward is enabled (Motor does not
rotate in reverse.)
02:
Only Reverse is enabled (Motor does not
rotate in forward.)
7-5-6
Permission of RUN Command
Parameter
No.
Function name
Data
Default
data
Unit
C001 to
C007
Multi-function Input S1 to
S7 Selection
84:
ROK (Permission of RUN command)
−
−
Output
frequency
ROK input
RUN command
FW/RV input
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...