![Omron SYSDRIVE MX2 SERIES User Manual Download Page 158](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918158.webp)
4 Parameter List
4 - 24
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
*1. When the safety function selector switch is ON, C003 and C004 are forcibly allocated to 77 (GS1) and 78 (GS2), respec-
tively. You cannot set 77(GS1) and 78(GS2) manually. If you turn ON and then OFF the safety function selector switch,
C003 and C004 are set to 255 (no: No allocation).
The 3G3MX2-V1 Series Inverter is currently under application for safety standards.
4-3-3
Group C: Multi-function Terminal Function Parameters
Parameter
No.
Function
name
Monitor or data range
Default
data
Set
data
Setting
during
RUN
Changes
during
RUN
Unit
Page
Mu
lti-fu
ncti
on inp
ut
termina
ls
C001
Multi-function
Input S1 Selec-
tion
00: FW (Forward)
01: RV (Reverse)
02: CF1 (Multi-step speed setting binary 1)
03: CF2 (Multi-step speed setting binary 2)
04: CF3 (Multi-step speed setting binary 3)
05: CF4 (Multi-step speed setting binary 4)
06: JG (Jogging)
07: DB (External DC injection braking)
08: SET (2nd control)
09: 2CH (2-step acceleration/deceleration)
11: FRS (Free-run stop)
12: EXT (External trip)
13: USP (Power recovery restart prevention function)
14: CS (Commercial switching)
15: SFT (Soft lock)
16: AT (Analog input switching)
18: RS (Reset)
19: TH (PTC thermistor thermal protection, C005 only)
20: STA (3-wire start)
21: STP (3-wire stop)
22: F/R (3-wire forward/reverse)
23: PID (PID disabled)
24: PIDC (PID integral reset)
27: UP (Remote operation accelerated)
28: DWN (Remote operation decelerated)
29: UDC (Remote operation data clear)
31: OPE (Forced operator function)
32: SF1 (Multi-step speed setting bit 1)
33: SF2 (Multi-step speed setting bit 2)
34: SF3 (Multi-step speed setting bit 3)
35: SF4 (Multi-step speed setting bit 4)
36: SF5 (Multi-step speed setting bit 5)
37: SF6 (Multi-step speed setting bit 6)
38: SF7 (Multi-step speed setting bit 7)
39: OLR (Overload limit switching)
40: TL (Torque limit enabled)
41: TRQ1 (Torque limit switching 1)
42: TRQ2 (Torque limit switching 2)
44: BOK (Brake confirmation)
46: LAC (LAD cancel)
47: PCLR (Current position clear)
50: ADD (Set frequency A145 addition)
51: F-TM (Forced terminal block)
52: ATR (Torque command input permission)
53: KHC (Integrated power clear)
56: MI1 (General-purpose input 1)
57: MI2 (General-purpose input 2)
58: MI3 (General-purpose input 3)
59: MI4 (General-purpose input 4)
60: MI5 (General-purpose input 5)
61: MI6 (General-purpose input 6)
62: MI7 (General-purpose input 7)
65: AHD (Analog command held)
66: CP1 (Position command selection 1)
67: CP2 (Position command selection 2)
68: CP3 (Position command selection 3)
69: ORL (Origin search limit signal)
70: ORG (Origin search startup signal)
73: SPD (Speed/Position switching)
77: GS1 (GS1 input, C003 only)
78: GS2 (GS2 input, C004 only)
81: 485 (Start co-inverter communication)
82: PRG (DriveProgramming start)
83: HLD (Retain output frequency)
84: ROK (Permission of RUN command)
85: EB (Rotation direction detection, C007 only)
86: DISP (Display fixed)
91: PSET (Preset position)
255: no (No allocation)
00
(FW)
Disabled Enabled
−
P. 5-48
P. 7-18
C002
Multi-function
Input S2 Selec-
tion
01
(RV)
Disabled Enabled
C003
Multi-function
Input S3 Selec-
tion
*1
18
(RS)
Disabled Enabled
C004
Multi-function
Input S4 Selec-
tion
*1
12
(EXT)
Disabled Enabled
C005
Multi-function
Input S5 Selec-
tion
02
(CF1)
Disabled Enabled
C006
Multi-function
Input S6 Selec-
tion
03
(CF2)
Disabled Enabled
C007
Multi-function
Input S7 Selec-
tion
06
(JG)
Disabled Enabled
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...