4 Parameter List
4 - 20
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
*1. The 3G3MX2-V1 Series Inverter does not provide the high-frequency mode.
*2. The default data was changed from the previous model.
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Setting
during
RUN
Changes
during
RUN
Unit
Page
Au
xi
liary function
b075
Ambient Tempera-
ture
−
10 to 50
40
Enabled
Enabled
°C
P. 7-85
b078
Integrated Power
Clear
00: Clear disabled
00
Enabled
Enabled
−
P. 7-9
01: Clear with the Enter key
b079
Integrated Power
Display Scale
1. to 1000.
1.
Enabled
Enabled
−
b082
Starting
Frequency
0.01 to 9.99
*1
1.50
*2
Disabled
Enabled
Hz
P. 7-35
b083
Carrier Frequency
2.0 to 15.0 or 10.0 (Heavy load/Light
load)
*1
This parameter requires derating.
10.0/
2.0
*1
Disabled
Enabled
kHz
P. 7-31
b084
Initialization
Selection
00: Initialization
disabled
00
Disabled Disabled
−
P. 5-6
01: Clearing
Fault
Monitor
02: Initialize
data
03: Clear fault monitor
+
Initialize data
04: Clear fault monitor
+
Initialize data
+
Clear DriveProgramming
b085
Initialization Data
Selection
Do not change from 00.
00
Disabled Disabled
−
b086
Frequency Con-
version Coefficient
0.01 to 99.99
1.00
Enabled
Enabled
−
P. 7-6
b087
STOP Key Selec-
tion
00: Enabled
00
Disabled
Enabled
−
P. 5-42
01: Disabled
02: Only RESET enabled
b088
Free-run Stop
Selection
00: 0-Hz
restart
00
Disabled
Enabled
−
P. 5-39
01: Frequency
matching
restart
02: Frequency pull-in restart
b089
Automatic Carrier
Reduction
00: Disabled
01
Disabled Disabled
−
P. 7-32
01: Enabled (dependent on current)
02: Enabled (dependent on cooling
fin temperature)
b090
Usage Rate of
Regenerative
Braking
0.0: Regenerative braking not active
0.1 to 100.0 (limited by setting in
b097)
0.0
Disabled
Enabled
%
P. 5-65
b091
Stop Selection
00: Deceleration
stop
00
Disabled
Enabled
−
P. 5-39
01: Free-run
stop
b092
Cooling Fan Oper-
ation
00: Always
enabled
01
Disabled
Enabled
−
P. 7-84
01: Enabled only during operation
(including 5 minutes after power on/
stop)
02: Dependent on fin temperature
b093
Total Fan Opera-
tion Time Clear
00: Clear
disabled
00
Disabled Disabled
−
01: Clear with the Enter key
b094
Initialization Target
Setting
00: All
data
00
Disabled Disabled
−
P. 5-6
01: All data other than terminals/
communications
02: U*** registration function only
03: Other than U*** registration
function and b37
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...