![Omron SYSDRIVE MX2 SERIES User Manual Download Page 480](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918480.webp)
8 Communications Functions
8 - 68
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1363 hex
1362 hex
Regenerative Brak-
ing ON Level
b096
R/W
200-V class: 330 to 380
1 [V]
P. 5-65
400-V class: 660 to 760
1364 hex
1363 hex
Braking Resistor
Value
b097
R/W
Minimum connection resis-
tance to 6000
0.1 [
Ω
]
1365 to
1366 hex
−
Reserved
−
−
−
−
−
1367 hex
1366 hex
Free V/f Frequency
1
b100
R/W 0. to Free V/f Frequency 2
1 [Hz]
P. 5-9
1368 hex
1367 hex
Free V/f Voltage 1
b101
R/W 0 to 8000
0.1 [V]
1369 hex
1368 hex
Free V/f Frequency
2
b102
R/W
Free V/f Frequency 1 to
Free V/f Frequency 3
1 [Hz]
136A hex
1369 hex
Free V/f Voltage 2
b103
R/W 0 to 8000
0.1 [V]
136B hex
136A hex
Free V/f Frequency
3
b104
R/W
Free V/f Frequency 2 to
Free V/f Frequency 4
1 [Hz]
136C hex
136B hex
Free V/f Voltage 3
b105
R/W 0 to 8000
0.1 [V]
136D hex
136C hex
Free V/f Frequency
4
b106
R/W
Free V/f Frequency 3 to
Free V/f Frequency 5
1 [Hz]
136E hex
136D hex
Free V/f Voltage 4
b107
R/W 0 to 8000
0.1 [V]
136F hex
136E hex
Free V/f Frequency
5
b108
R/W
Free V/f Frequency 4 to
Free V/f Frequency 6
1 [Hz]
1370 hex
136F hex
Free V/f Voltage 5
b109
R/W 0 to 8000
0.1 [V]
1371 hex
1370 hex
Free V/f Frequency
6
b110
R/W
Free V/f Frequency 5 to
Free V/f Frequency 7
1 [Hz]
1372 hex
1371 hex
Free V/f Voltage 6
b111
R/W 0 to 8000
0.1 [V]
1373 hex
1372 hex
Free V/f Frequency
7
b112
R/W
Free V/f Frequency 6 to
400
*1
1 [Hz]
1374 hex
1373 hex
Free V/f Voltage 7
b113
R/W 0 to 8000
0.1 [V]
1375 to
137A hex
−
Reserved
−
−
−
−
−
137B hex
137A hex
Brake Control
Function Selection
b120
R/W
00:
Disabled
−
P. 6-25
01:
Enabled (DC Injec-
tion braking enabled
during stop)
02:
Enabled (DC Injec-
tion braking disabled
during stop)
137C hex
137B hex
Brake Release Wait
Time
b121
R/W 0 to 500
0.01 [s]
137D hex
137C hex
Acceleration Wait
Time on Brake
Control
b122
R/W 0 to 500
0.01 [s]
137E hex
137D hex
Stop Wait Time on
Brake Control
b123
R/W 0 to 500
0.01 [s]
137F hex
137E hex
Brake Error
Detection Time
b124
R/W 0 to 500
0.01 [s]
1380 hex
137F hex
Brake Release
Frequency
b125
R/W 0 to 40000
0.01
[Hz]
1381 hex
1380 hex
Brake Release
Current
b126
R/W 0 to 2000
0.1 [%]
1382 hex
1381 hex
Brake Force
Frequency
b127
R/W 0 to 40000
0.01
[Hz]
1383 hex
−
Reserved
−
−
−
−
−
1384 hex
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...