![Omron SYSDRIVE MX2 SERIES User Manual Download Page 167](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918167.webp)
4 - 33
4 Parameter List
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
4-3 Ext
end
ed F
unc
tion
Mod
e
4
4-
3-4 Gro
up H: Motor
Contr
ol Par
ameters
*1. These parameters are newly added to the 3G3MX2-V1 Series.
Control p
aram
e
ter
s
H032
1st Motor Parameter L
(Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
Dependent
on capacity
Disabled Disabled
mH
P. 6-4
H232
2nd Motor Parameter L
(Auto-tuning Data)
Dependent
on capacity
Disabled Disabled
H033
1st Motor Parameter Io
(Auto-tuning Data)
0.01 to 99.99
100.0 to 655.3
Dependent
on capacity
Disabled Disabled
A
H233
2nd Motor Parameter
Io
(Auto-tuning Data)
Dependent
on capacity
Disabled Disabled
H034
1st Motor Parameter J
(Auto-tuning Data)
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Dependent
on capacity
Disabled Disabled
kgm
2
H234
2nd Motor Parameter J
(Auto-tuning Data)
Dependent
on capacity
Disabled Disabled
H050
V/f Control With
Speed Feedback Slip
Compensation
Proportional Gain
0.00 to 10.00
0.20
Enabled
Enabled
time
P. 6-24
H051
V/f Control With
Speed Feedback Slip
Compensation
Integral Gain
0. to 1000.
2.
Enabled
Enabled
s
H102
PM Motor Parameter
Selection
*1
00: Standard
PM
motor
parameter
00
Disabled Disabled
−
P. 6-61
01: Auto-tuning
parameter
H103
PM Motor Capacity
*1
0.1/0.2/0.4/0.55/0.75/1.1/1.5/
2.2/3.0/3.7/4.0/5.5/7.5/11.0/
15.0/18.5
Maximum
applicable
motor
capacity
Disabled Disabled
kW
H104
PM Motor Pole
Number
*1
2/4/6/8
10 to 488: Do not set.
Dependent
on capacity
Disabled Disabled
pole
H105
PM Motor Rated
Current
*1
0.00 to 1.00
×
Rated current
Dependent
on capacity
Disabled Disabled
A
H106
PM Motor
Parameter R
*1
0.001 to 9.999
10.00 to 65.53
Dependent
on capacity
Disabled Disabled
Ω
H107
PM motor
Parameter Ld
*1
0.01 to 99.99
100.0 to 655.3
Dependent
on capacity
Disabled Disabled
mH
H108
PM motor
Parameter Lq
*1
0.01 to 99.99
100.0 to 655.3
Dependent
on capacity
Disabled Disabled
mH
H109
PM motor
Parameter Ke
*1
0001 to 9999
(0.0001 to 0.9999)
1.000 to 6.553
Dependent
on capacity
Disabled Disabled
Vp/
(rad/s)
H110
PM motor
Parameter J
*1
0.001 to 9.999
10.00 to 99.99
100.0 to 999.9
1000. to 9999.
Dependent
on capacity
Disabled Disabled
kgm
2
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Setting
during
RUN
Changes
during
RUN
Unit
Page
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...