5 Basic Settings
5 - 28
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
To switch between the analog voltage and analog current inputs to set the frequency reference, set the
parameters as shown in the table below.
This enables switching between the frequency reference input (voltage reference) and frequency refer-
ence input (current reference) terminals.
To switch between these analog input signals, use the terminal AT (Analog input switching) allocated to
a multi-function input terminal.
When the terminal AT is input, the frequency reference input (current reference) terminal is enabled.
• Frequency reference input (Voltage reference), between FV and SC: 0 to 10 VDC
• Frequency reference input (Current reference), between FI and SC: 4 to 20 mA
Note
By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
To switch between an analog voltage input and the volume control on the Digital Operator (Model:
3G3AX-OP01) to set the frequency reference, set the parameters as shown in the table below.
This enables switching between the frequency reference input (voltage reference) and the volume con-
trol on the 3G3AX-OP01.
To switch the reference input, use the terminal AT (Analog input switching) allocated to a multi-function
input terminal.
When the terminal AT is input, the volume control on Digital Operator (Model: 3G3AX-OP01) is
enabled.
• Frequency reference input (Voltage reference), between FV and SC
:
0 to 10 VDC
• Volume control on Digital Operator (Model: 3G3AX-OP01)
Note
By default, each analog input signal is set to reach the maximum frequency at 9.8 V or 19.8 mA.
Using an Analog Voltage Input or Analog Current Input by Switching
Parameter No.
Function name
Data
Default data
Unit
A001/A201
1st/2nd Frequency
Reference Selection
01:
Control circuit terminal block
(Analog input)
02
−
A005
FV/FI Selection
00: Switch between FV (Voltage)
and FI (Current)
00
−
C001 to C007
Multi-function Input
S1 to S7 Selection
16: AT (Analog input switching)
−
−
Using an Analog Voltage Input and Volume Control by Switching
Parameter No.
Function name
Data
Default data
Unit
A001/A201
1st/2nd Frequency
Reference Selection
01:
Control circuit terminal block
(Analog input)
02
−
A005
FV/FI Selection
02:
Switch between FV (Voltage)
and volume via terminal AT
(Enabled only when
3G3AX-OP01 is used.)
00
−
C001 to C007
Multi-function Input
S1 to S7 Selection
16:
AT (Analog input switching)
−
−
V
A
V
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...