![Omron SYSDRIVE MX2 SERIES User Manual Download Page 227](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918227.webp)
5 - 51
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-9 Mu
lti-fun
ctio
n
In
pu
t Setting
s
5
5-
9-5 Multi-step S
pe
ed Operation Fu
nction
• Setting the Multi-function Input S1 to S7 Selection (C001 to C007) to 32 (SF1) to 38 (SF7) enables
the selection of the multi-step speed 0 to 7.
• Use the Multi-step Speed Reference 1 to 7 (A021 to A027) to set the frequency for SF1 to SF7.
• Use the 1st/2nd Frequency Reference Selection (A001/A201) to set the 1st/2nd Multi-step Speed
Reference 0 (A020/A220).
Set the 1st/2nd Frequency Reference Selection (A001/A201) to 02 (Digital Operator: F001) to enable
the 1st/2nd Multi-step Speed Reference 0 (A020/A220).
If A001/A201 are set to 01 (Control circuit terminal block: Analog input), the analog input is used as
the frequency reference to set the 1st/2nd Multi-step Speed Reference 0.
Bit Operation
Parameter
No.
Function name
Data
Default data
Unit
C001 to
C007
Multi-function Input S1 to S7
Selection
32: SF1 (Multi-step speed setting bit 1)
−
−
33: SF2 (Multi-step speed setting bit 2)
34: SF3 (Multi-step speed setting bit 3)
35: SF4 (Multi-step speed setting bit 4)
36: SF5 (Multi-step speed setting bit 5)
37: SF6 (Multi-step speed setting bit 6)
38: SF7 (Multi-step speed setting bit 7)
Multi-step
speed
SF7
SF6
SF5
SF4
SF3
SF2
SF1
0th
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1st
Disabled Disabled Disabled Disabled Disabled Disabled ON
2nd
Disabled Disabled Disabled Disabled Disabled ON
OFF
3rd
Disabled Disabled Disabled Disabled ON
OFF
OFF
4th
Disabled Disabled Disabled ON
OFF
OFF
OFF
5th
Disabled Disabled ON
OFF
OFF
OFF
OFF
6th
Disabled ON
OFF
OFF
OFF
OFF
OFF
7th
ON
OFF
OFF
OFF
OFF
OFF
OFF
Note When several terminals simultaneously turn ON, prior-
ity is given to the terminal with the smallest number.
“Disabled” in the above table indicates that speed is
selected regardless of the ON/OFF status.
SF1
SF2
SF3
SF4
FW
SF5
SF6
SF7
SF8
Frequency from
Digital Operator or
external analog
input terminal
1st
2nd
3rd
4th
7th
5th
6th
0th
1st
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...