![Omron SYSDRIVE MX2 SERIES User Manual Download Page 439](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918439.webp)
8 - 27
8 Communications Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
8
-7 Mo
dbu
s Map
p
ing
Fu
nct
ion
8
8-7
-3 Comp
ressed Single-wo
rd Registers
z
Inverter control input register No. 1F01 hex
z
Inverter status monitor register No. 1E01 hex
1F33 hex
1F32 hex 1st Deceleration Time 1
F003
R/W
0 to 65535
0.01 [s]
1F34 hex
1F33 hex
1st Multi-step Speed
Reference 0
A020
R/W
0/Starting Frequency to 1st
Maximum Frequency
0.01
[Hz]
1F35 hex
1F34 hex
Multi-step Speed
Reference 1
A021
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F36 hex
1F35 hex
Multi-step Speed
Reference 2
A022
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F37 hex
1F36 hex
Multi-step Speed
Reference 3
A023
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F38 hex
1F37 hex 1st Frequency Upper Limit
A061
R/W
0/Frequency Lower Limit to
Maximum Frequency
0.01
[Hz]
1F39 hex
1F38 hex 1st Frequency Lower Limit
A062
R/W
0 to Frequency Upper Limit
0.01
[Hz]
1F3A hex
1F39 hex
Acceleration Stop Fre-
quency
A069
R/W
0.00 to Starting Frequency:
Disabled
Frequency above Starting
Frequency to 40000
0.01
[Hz]
1F3B hex 1F3A hex
Frequency Addition
Amount Setting
A145
R/W
0 to 40000
0.01
[Hz]
1F3C hex 1F3B hex
Deceleration Stop Fre-
quency
A154
R/W
0.00 to Starting Frequency:
Disabled
Frequency above Starting
Frequency to 40000
0.01
[Hz]
1F3D hex 1F3C hex
PID Sleep Operation
Level
A156
R/W
0 to 40000
0.01
[Hz]
1F3E hex 1F3D hex
Frequency Matching
Lower Limit Frequency
b007
R/W
0 to 40000
0.01
[Hz]
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Name
−
−
In7
In6
In5
In4
In3
In2
In1
−
−
RS
EXT
Dir
Opr
−
Opr
RUN command (0: Stop/ 1: RUN)
In3
Multi-function input S3
Dir
Rotation direction command (0: Forward/1: Reverse)
In4
Multi-function input S4
EXT
External trip
In5
Multi-function input S5
RS
Reset
In6
Multi-function input S6
In1
Multi-function Input S1
In7
Multi-function Input S7
In2
Multi-function Input S2
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Name
ONT
RNT
TRQ
UV
−
OTQ
FA3
AL
OD
OL
FA2
FA1
RUN
−
IRDY
Dir
Dir
Rotation direction (0: Forward/1: Reverse)
AL
Alarm
IRDY
Inverter ready
FA3
Set-frequency only
RUN
During RUN
OTQ
Overtorque/Undertorque
FA1
Constant speed reached
UV
Undervoltage
FA2
Set frequency exceeded
TRQ
Torque limit
OL
Overload warning
RNT
RUN time over
OD
Excessive PID deviation
ONT
Power ON time over
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolu-
tion
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...