5 Basic Settings
5 - 24
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-5
Frequency Reference Settings
• Select the input method for the frequency reference in 1st/2nd Frequency Reference Selection
(A001/A201).
• When the multi-step speed reference function is used (by setting the multi-function input terminals for
the Multi-step Speed Reference 0 to 15), the setting in A001/A201 is enabled only for the Multi-step
Speed Reference 0.
The values set in the Multi-step Speed Reference 1 to 15 (A021 to A035 ) are used as the frequency
references for the multi-step speed reference 1 to15.
• The frequency reference value selected in the 1st/2nd Frequency Reference Selection can be
checked in the Output Frequency Setting/Monitor (F001). In addition, when A001/A201 is set to 02
(Digital Operator (F001)), the frequency reference can be changed in F001.
• When the Multi-function Input S1 to S7 Selection is set to 31 (OPE: Forced operator function) or 51
(F-TM: Forced terminal block), the setting has priority over the 1st/2nd Frequency Reference Selec-
tion (A001/A201) and 1st/2nd RUN Command Selection (A002/A202).
When each terminal is input, the frequency reference and RUN command from the Digital Operator
or the control terminal are enabled.
The values set in the Multi-step Speed Reference 1 to 15 have priority over the forced operator func-
tion and forced terminal block.
*1. To enable the switching to the 2nd control, set one of the Multi-function Input S1 to S7 Selection (C001 to
C007) to 08 (SET) and turn ON that terminal.
*2. This setting is enabled when the Digital Operator with the volume control (Model: 3G3AX-OP01) is con-
nected.
*3. Refer to
7-5-7 Frequency Calculation Function
on page 7-39.
5-5-1
Frequency Reference Selection
Parameter
No.
Function name
Data
Default data
Unit
A001/A201
1st/2nd Frequency
Reference Selec-
tion
*1
00:
Digital Operator (Volume)
*2
02
−
01:
Control circuit terminal block
(Analog input)
02:
Digital Operator (F001)
03: Modbus
communication
04:
Option
06:
Pulse train frequency
07:
DriveProgramming
10:
Operation function output
*3
F001
Output Frequency
Setting/Monitor
0.00, Starting Frequency to 1st/2nd Max-
imum Frequency
When the PID function is enabled: 0.0 to
100.0
6.00
Hz
%
Related functions
A005, A141 to A143, A145, A146
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...