5 Basic Settings
5 - 66
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Precautions for Correct Use
• To use the built-in regenerative braking function of the inverter, be sure to set the Usage Rate
of Regenerative Braking (b090) and the Regenerative Braking Selection (b095) to 01 or 02. If
you do not set both parameters, the function cannot work.
• Setting the Regenerative Braking ON Level (b096) to the incoming voltage or lower causes
the built-in regenerative braking function to be always active, which results in overheating or
burning of the braking resistor. Be sure to set this to a value higher than the incoming voltage
multiplied by the square root of 2.
Set b096 to 380 VDC or higher for 240 VAC of the incoming voltage and to 750 VDC or
higher for 480 VAC of the incoming voltage, respectively.
• To use the regenerative braking function, connect external braking resistor(s) or external
regenerative braking unit(s) according to the description of External Braking Resistor Con-
nection Terminal/Regenerative Braking Unit Connection Terminal in
2-3-4 Wiring for Main
Circuit Terminals
on page 2-15.
Be sure to install a circuit that detects overheating of the braking resistor(s) and the regener-
ative braking unit(s) via alarm contacts (thermal relay output terminals) and shuts off the
input power supply of the inverter.
Parameter
No.
Function name
Data
Default
data
Unit
b090
Usage Rate of Regen-
erative Braking
0.0: Regenerative braking not active
0.1 to 100.0 (Limited by b097) The usage rate must
be set as a percentage (%) as follows:
Allowable braking frequency [%] of the connected
braking resistor or lower.
Exceeding the set usage rate causes the protective
function to be activated, which results in a trip.
0.0
%
b095
Regenerative Braking
Selection
00:
Disabled
00
−
01:
Enabled (Disabled during stop)
02:
Enabled (Enabled during operation and stop)
b096
Regenerative Braking
ON Level
200-V class: 330 to 380 VDC
*1
*1. For the Regenerative Braking ON Level, set the internal main circuit DC voltage of the inverter.
200-V
class:
360 V
V
400-V class: 660 to 760 VDC
*1
400-V
class:
720 V
b097
Braking Resistor Value Minimum connection resistance to 600.0
Set the resistance of the braking resistor actually
connected to the inverter.
Then, the inverter automatically calculates the upper
limit value allowable in b090.
This allows you to consider only the allowable brak-
ing frequency (%) of the braking resistor when set-
ting b090.
Minimum
connec-
tion resis-
tance for
capacity
Ω
t1
t2
t3
ON
ON
ON
=
×
100 s
Regenerative
braking function
activated
Usage rate [%]
100 s
(t1
+
t2
+
t3)
100
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...