![background image](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918392.webp)
7 Other Functions
7 - 82
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
The inverter outputs the frequency arrival signal only when the inverter reaches the frequency set in the
Arrival Frequency During Acceleration 1/2 (C042/C045) or Arrival Frequency During Deceleration 1/2
(C043/C046).
fon: 1% of maximum frequency
foff: 2% of maximum frequency
If the total RUN time or power ON time of the inverter exceeds the RUN Time/Power ON Time Detection
Level (b034), the inverter will output the RUN time over (RNT) or Power ON time over (ONT) signal.
Allocate the Multi-function Output P1/P2 Selection (C021/C022) or Multi-function Relay Output (MA,
MB) Function Selection (C026) to 11 (RNT: RUN time over).
Set the RUN Time/Power ON Time Detection Level (b034).
Allocate the Multi-function Output P1/P2 Selection (C021/C022) or Multi-function Relay Output (MA,
MB) Function Selection (C026) to 12 (ONT: Power ON time over).
Set the RUN Time/Power ON Time Detection Level (b034).
Set-frequency Only Signal (C021, C022, C026 = 06: FA3, 25: FA5)
7-8-10 RUN Time/Power ON Time Over (RNT/ONT)
Parameter
No.
Function name
Data
Default
data
Unit
b034
RUN Time/Power ON
Time Detection Level
0.
Function is disabled
0.
10 hex
1. to 9999.
Set in increments of 10 hours (10 to 99,990 h)
1000 to 6553 (10000 to 65530)
Set in increments of 100 (10) hours
(100,000 to 655,300 h)
C021, C022
C026
Multi-function Output
P1/P2 Selection,
Multi-function Relay Out-
put (MA, MB) Function
Selection
11:
RNT (RUN time over)
−
−
12:
ONT (Power ON time over)
Related functions
d016, d017
RUN Time Over (C021, C022, C026 = 11: RNT)
Power ON Time Over (C021, C022, C026 = 12: ONT)
f
on
f
off
C042/C045
C043/C046
f
on
f
off
Output frequency
FA3/FA5 output
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...