5 - 61
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-
11
T
o
rq
ue
B
o
os
t Fu
nc
tion
Se
tti
n
gs
5
5-
11-1
Tor
que Boost
• In the 3G3MX2-V1 Series Inverter, the default data for A041/A241 were changed to Automatic torque
boost (A041/A241 = 01).
With this setting, the inverter increases the output voltage automatically depending on the load condi-
tion. In other words, the output voltage generated when the automatic torque boost is enabled is the
sum of manual torque boost voltage and the automatic torque boost voltage.
• To use the automatic torque boost function effectively, set the 1st/2nd Motor Capacity (H003/H203)
and the 1st/2nd Motor Pole Number (H004/H204) correctly according to your motor.
• To avoid possible overcurrent tripping during deceleration, set the AVR Selection (A081) to 00
(Always ON).
• To enable the slip compensation function in addition to the voltage compensation provided by the
automatic torque boost function, first set the 1st/2nd Automatic Torque Boost Slip Compensation
Gain (A047/A247) to 100%.
• If the automatic torque boost does not provide the intended performance characteristics, adjust it for
each adjustment item shown in the following table.
Automatic Torque Boost
Phenomenon
Adjustment method
Adjustment item
Torque is insufficient at
low speeds. (Motor
does not rotating at
low speeds.)
(1)
Gradually increase the Automatic Torque Boost Voltage
Compensation Gain.
A046/A246
(2)
Set the Automatic Torque Boost Slip Compensation Gain to
100. Then, increase the set value gradually.
A047/A247
(3)
Gradually increase the Manual Torque Boost Voltage.
A042/A242
(4)
Decrease the Carrier Frequency.
b083
Overcurrent trip
occurs when load is
applied.
(1)
Gradually decrease the Automatic Torque Boost Voltage
Compensation Gain.
A046/A246
(2)
Set the Automatic Torque Boost Slip Compensation Gain to
100. Then, decrease the set value gradually.
A047/A247
(3)
Gradually decrease the Manual Torque Boost Voltage.
A042/A242
(4)
Gradually decrease the Overload Limit Parameter.
b023/b223/b026
Phenomenon
Adjustment method
Adjustment item
Rotation speed
decreases when load
is applied.
Set the Automatic Torque Boost Slip Compensation Gain to 100
and gradually increase the value.
A047/A247
Rotation speed
increases when load is
applied.
Set the Automatic Torque Boost Slip Compensation Gain to 100
and gradually decrease the value.
A047/A247
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...