7 - 81
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-
8 Fu
nct
ion
s Relat
ed to
Prot
ectio
n, W
arnin
g, an
d V
ariou
s O
u
tp
ut
Si
gnal
s
7
7-8
-9 F
requency Arrival Signal (F
A2 to F
A
5
)
The inverter outputs the frequency arrival signal when the output frequency reaches the set level.
Allocate the Multi-function Output P1/P2 Selection (C021/C022) or Multi-function Relay Output (MA,
MB) Function Selection (C026) to 02 (FA2: Set frequency exceeded signal), 06 (FA3: Set frequency
only signal), 24 (FA4: Set frequency exceeded signal 2) or 25 (FA5: Set frequency only signal 2).
The hysteresis of the signals FA2 (02) and FA4 (24) is calculated as follows.
The hysteresis of the signals FA3 (06) and FA4 (25) during acceleration is calculated as follows.
The hysteresis of these signals during deceleration is calculated as follows.
The inverter outputs the frequency arrival signal when the inverter reaches the frequency set in the
Arrival Frequency During Acceleration 1/2 (C042/C045) or Arrival Frequency During Deceleration 1/2
(C043/C046) or higher.
7-8-9
Frequency Arrival Signal (FA2 to FA5)
ON
: (Set frequency)
−
(1% of maximum frequency) [Hz]
OFF
: (Set frequency)
−
(2% of maximum frequency) [Hz]
ON
: (Set frequency)
−
(1% of maximum frequency) [Hz]
OFF
: (Set frequency)
+
(2% of maximum frequency) [Hz]
ON
: (Set frequency)
+
(1% of maximum frequency) [Hz]
OFF
: (Set frequency)
−
(2% of maximum frequency) [Hz]
Parameter
No.
Function name
Data
Default
data
Unit
C042/C045
Arrival Frequency During
Acceleration 1/Arrival Fre-
quency During Accelera-
tion 2
0.00
Not output arrival signal during acceleration
0.00
Hz
0.01 to 400.0
Output arrival signal during acceleration
C043/C046
Arrival Frequency During
Deceleration 1/Arrival Fre-
quency During Decelera-
tion 2
0.00
Not output arrival signal during deceleration
0.00
Hz
0.01 to 400.0
Output arrival signal during deceleration
C021, C022
C026
Multi-function Output
P1/P2 Selection
Multi-function Relay Out-
put (MA, MB) Function
Selection
02:
FA2 (Set frequency exceeded signal)
−
−
06:
FA3 (Set-frequency only signal)
24:
FA4 (Set frequency exceeded signal 2)
25:
FA5 (Set-frequency only signal 2)
Set Frequency Exceeded Signal (C021, C022, C026 = 02: FA2, 24: FA4)
f
on
f
off
C042/C045
C043/C046
Output frequency
FA2/FA4 output
fon: 1% of maximum frequency
foff: 2% of maximum frequency
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...