7 Other Functions
7 - 54
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-6
Digital Operator and Operation Functions
This section describes the Digital Operator and other operation functions.
Use this function to protect various parameter settings against changes. This helps prevent data rewrit-
ing due to erroneous operation.
Use the table below to select which type of soft lock you want to apply.
To use this function from a multi-function input terminal, allocate the Multi-function Input S1 to S7 Selec-
tion (C001 to C007) to 15 (SFT).
Setting b031 to 10 (Data can be changed during RUN) enables you to change the parameters marked
with Enabled under “Changes during operation” in
Section 4 Parameter List
during operation.
Alternatively, you can use the password function to protect parameter data. Refer to
7-6-9 Password
Function
on page 7-57.
Precautions for Correct Use
When the Soft Lock Selection (b031) is set to prohibit changes of the initialization-related
parameters (b084, b094, b180), the initialization cannot be executed. Change the Soft Lock
Selection (b031) to enable the initialization.
For details on the parameter initialization, refer to
5-1-2 Parameter Initialization
on page 5-6.
7-6-1
Soft Lock Function (SFT)
Parameter
No.
Function name
Data
Terminal
SFT
Description
Default
data
Unit
b031
Soft Lock Selection
00
ON
Rewriting enabled only for
b031.
01
−
OFF
Soft lock function disabled
(Normal operation).
01
ON
Rewriting enabled only for
b031 and frequency set-
tings (F001, A020, A220,
A021 to A035, A038).
OFF
Soft lock function disabled
(Normal operation).
02
−
Rewriting enabled only for
b031.
03
−
Rewriting enabled only for
b031 and frequency set-
tings (F001, A020, A220,
A021 to A035, A038).
10
−
Changes enabled during
RUN.
(Only functions listed in
Sec-
tion 4 Parameter List
can be
changed.)
C001 to
C007
Multi-function Input S1
to S7 Selection
15:
SFT (Soft lock)
−
−
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...