![Omron SYSDRIVE MX2 SERIES User Manual Download Page 471](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918471.webp)
8 - 59
8 Communications Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
8-9 Mo
db
us Co
mm
un
icatio
n Dat
a L
ist
s
8
8-9
-4 Group A/b
/C/H/P Register List
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1288 to
12A4 hex
−
Reserved
−
−
−
−
−
12A5 hex
12A4 hex
Acceleration Curve
Parameter
A131
R/W
01 (Small curve) to 10
(Large curve)
−
P. 5-34
12A6 hex
12A5 hex
Deceleration Curve
Parameter
A132
R/W
01 (Small curve) to 10
(Large curve)
−
12A7 to
12AE
hex
−
Reserved
−
−
−
−
−
12AF hex 12AE hex
Calculation
Frequency
Selection 1
A141
R/W
00:
Digital Operator (A020/A220)
−
P. 7-39
01:
Volume
*1
02:
Voltage (FV) input
03:
Current (FI) input
04:
Modbus communication
05:
Option
07:
Pulse train frequency
12B0 hex
12AF hex
Calculation
Frequency
Selection 2
A142
R/W
00:
Digital Operator (A020/A220)
−
01:
Volume
*1
02:
Voltage (FV) input
03:
Current (FI) input
04:
Modbus communication
05:
Option
07:
Pulse train frequency
12B1 hex
12B0 hex
Calculation Function
Operator Selection
A143
R/W
00:
Addition (A141
+
A142)
−
01:
Subtraction (A141
−
A142)
02:
Multiplication
(A141
×
A142)
12B2 hex
−
Reserved
−
−
−
−
−
12B3 hex
12B2 hex
Frequency Addition
Amount Setting
A145
(HIGH)
R/W
0 to 40000
*2
0.01
[Hz]
*3
P. 7-39
12B4 hex
12B3 hex
A145
(LOW)
R/W
12B5 hex
12B4 hex
Frequency Addition
Sign Selection
A146
R/W
00:
Frequency reference
+
A145
−
01:
Frequency reference
−
A145
12B6 to
12B8 hex
−
Reserved
−
−
−
−
−
12B9 hex
12B8 hex
EL-S Shape
Acceleration Curve
Ratio 1
A150
R/W 0 to 50
1 [%]
P. 5-34
12BA hex
12B9 hex
EL-S Shape
Acceleration Curve
Ratio 2
A151
R/W 0 to 50
1 [%]
12BB hex
12BA hex
EL-S Shape
Deceleration Curve
Ratio 1
A152
R/W 0 to 50
1 [%]
12BC hex
12BB hex
EL-S Shape
Deceleration Curve
Ratio 2
A153
R/W 0 to 50
1 [%]
*1. This setting is enabled when the Digital Operator with the volume control (Model: 3G3AX-OP01) is connected.
*2. The 3G3MX2-V1 Series Inverter does not provide the high-frequency mode.
*3. When the PID function is enabled, the data unit differs between read and write operations.
Set parameter values in units of 0.01 Hz for writing and in units of 0.1% (as 100% of the maximum frequency)
for reading.
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...