7 Other Functions
7 - 4
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-1
Monitor Mode
This section describes the output frequency, fault monitor during trip, and other monitor functions of the
inverter.
Use this function to display the output frequency of the inverter. The value is 0.00 when the inverter is
stopped.
The monitor display LED “Hz” is lit while the value of d001 is displayed.
Additional Information
• When the 1st/2nd Frequency Reference Selection (A001/A201) is set to 02 (Digital Operator:
F001), if the d001/d007 Data Setting Selection (b163) is set to 01 (Enabled), you can change
the Output Frequency Monitor (d001) by the Increment/Decrement key only during operation.
• The Output Frequency Monitor (d001) value is reflected on the Output Frequency Set-
ting/Monitor (F001) setting and stored to the EEPROM when you press the Enter key.
• Because the inverter updates the F001 value while displaying d001, the input value may not
be displayed immediately depending on the acceleration/deceleration time.
• The monitor value cannot be changed while the PID function is activated/stopped.
• In the individual input mode, it is not possible to change the frequency by simultaneously
pressing the Increment and Decrement keys.
Use this function to display the output current value of the inverter. The value is 0.0 when the inverter is
stopped.
The monitor display LED “A” is lit while the value of d002 is displayed.
7-1-1
Output Frequency Monitor [d001]
Parameter
No.
Function name
Data
Default
data
Unit
d001
Output Frequency
Monitor
0.00 to 99.99 (Displayed in increments of 0.01)
100.0 to 400.0 (Displayed in increments of 0.1)
−
Hz
b163
d001/d007 Data Set-
ting Selection
00:
Disabled
(Frequency cannot be changed in
d001/d007)
00
−
01:
Enabled
(Frequency can be changed in
d001/d007)
Related functions
A001, A201, F001, d007
7-1-2
Output Current Monitor [d002]
Parameter
No.
Function name
Data
Default
data
Unit
d002
Output Current Monitor
0.0 to 655.3
Minimal unit depends on inverter capacity.
−
A
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...