12 - 5
12 Options
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
12-2
Regen
erative
Braking
Unit
(Mo
d
el:
3G
3AX-RB
U
)
12
12-
2-1
S
pecificatio
ns
12-2 Regenerative Braking Unit
(Model: 3G3AX-RBU
)
12-2-1 Specifications
Built-in Resistor Type (Model: 3G3AX-RBU21/RBU22/RBU41)
Voltage class
3-phase 200-V class
3-phase 400-V class
Model
3G3AX-RBU21
3G3AX-RBU22
3G3AX-RBU41
*1
*1. To use the braking resistor (Model: 3G3AX-RAB/RBB/RBC) for the 400-V class regenerative braking unit, be sure
to remove the built-in resistor and connect two resistors of the same model in series. Using a 400-V class regen-
erative braking unit with only a single braking resistor connected may cause damage to the braking resistor.
Connection resistance
17
Ω
min.
17
Ω
min.
34
Ω
min.
Operating voltage (ON/OFF)
ON: 362.5 ± 5 V
OFF: 355 ± 5 V
(
−
5% or
−
10% setting available
*2
)
*2. Use DIP switches (SW1 to SW4) on the regenerative braking unit to set the number of connected units.
ON: 725 ± 5 V
OFF: 710 ± 5 V
(
−
5% or
−
10% setting
available
*2
)
Operation indication
LED ON (Lit)
Maximum number of units for parallel
interlocking operation
*2
5 units
Model
3G3AX-RBU21
3G3AX-RBU22
3G3AX-RBU41
*1
Cable length between regenerative
braking unit and inverter
5 m max.
Built-in
resistor
Internal resistance
120 W 180
Ω
120 W 20
Ω
120 W 180
Ω
×
2 in series
Allowable continuous ON time
10 s max.
0.5 s max.
10 s max.
Allowable operation
cycle
Cycle 1/10
(ON for 10 s/OFF for 90 s)
Cycle 1/80
(ON for 0.5 s/OFF for 40 s)
Cycle 1/10
(ON for 10 s/OFF for 90 s)
Power consumption
Instantaneous: 0.73 kW
Short-time rating: 120 W
Instantaneous: 6.6 kW
Short-time rating: 120 W
Instantaneous: 1.46 kW
Short-time rating: 240 W
Protective
function
Built-in resistor overheat
protection
Built-in relay specifications
Built-in resistor temperature: Relay trips at approximately 200°C or higher
and resets at approximately 170°C or lower.
Built-in thermal fuse (No resetting)
*3
*3. The built-in resistor has a thermal fuse. If the alarm terminals are not connected, the fuse may blow out in order
to prevent the overheating. If the fuse blows out, the regenerative braking unit must be repaired.
Contact rating: 250 VAC 200 mA (R load)
12 VDC 500 mA (R load)
42 VDC 200 mA (R load)
Minimum load: 1 mA
Operating
environment
Operating ambient temperature
−
10 to 50°C
Storage ambient temperature
−
20 to 65°C
Operating ambient humidity 20% to 90% (with no condensation)
Vibration resistance
5.9 m/s
2
(0.6 G) 10 to 55 Hz
Location
At a maximum altitude of 1,000 m (without corrosive gases or dust)
Weight [kg]
1.7
2.0
Paint color
Munselle 5Y7/1 (except for cooling fan with aluminum base color)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...