![Omron SYSDRIVE MX2 SERIES User Manual Download Page 370](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918370.webp)
7 Other Functions
7 - 60
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
The parameter group U consists of user parameters. Up to 32 user parameters can be registered as
desired. When registration is done, set the Display Selection (b037) to 02 (User setting). After that, you
will see only the functions registered with U001 to U032 in addition to d001, F001, and b037.
When the User Parameter Automatic Setting Function (b039) is set to 01 (Enabled), the parameters
with changed data are stored automatically in an ascending order from U001 to U032. This function is
useful as the change history.
The data (parameter setting) displayed on the screen is stored at the time when you press the Enter
key. This is also applicable for storing the monitor functions (d***).
U001 stores the most recent parameter data; U032 stores the oldest.
If the same parameter was changed, the previous change is deleted and the last one is stored. In addi-
tion, if the number of the parameters exceeds 32, the data is deleted from the oldest (U032).
Note
Be aware that changing the 039 value from 00 to 01 initializes (resets to “no”) all parameter data registered
to the user parameters U001 to U032.
7-6-10 User Parameter Setting Function
Parameter
No.
Function name
Data
Default
data
Unit
U001 to
U032
User Selection 1 to 32
no:
No registration
no
−
d001 to P196
Register any function code.
b037
Display Selection
02:
User setting
+
d001, F001, b037
00
*1
*1. The default data was changed from the previous model.
−
7-6-11 User Parameter Automatic Setting Function
Parameter
No.
Function name
Data
Default
data
Unit
b039
User Parameter Automatic Setting
Function
00:
Disabled
00
−
01:
Enabled
Related functions
U001 to U032
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...