7 Other Functions
7 - 28
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
You can set the output gain in the MP Gain Setting (C105) when the MP Selection (C027) is set to 00 to
02, 04 to 07, 10, or 12 (settings with PWM output).
When C027 is set to 08 (Digital current monitor), set the reference current value for the output pulses in
the Digital Current Monitor Reference Value (C030). The output will be made in proportion to this value,
so that the current value set in C030 produces an output frequency of 1440 Hz.
When C027 is set to 15 (Pulse train input monitor), you can set the output gain in the Pulse Train Out-
put MP Scale (C047) (to obtain an output of Input value
×
C047).
*1. 07 (LAD frequency) represents the frequency commanded by the inverter and is equivalent of the Output Fre-
quency Monitor (d001) value. 00 (Output frequency) represents a frequency value that takes into account the
aspects of vector control compensation (such as sensorless vector control) and even stabilization control.
When set to 00 (Output frequency), the parameter may produce an output that appears to be unstable at low
speeds, for example, when decelerating due to the overload limit function. In this case, set it to 07 (LAD fre-
quency) to obtain a stable output.
*2. Setting the Pulse Train Input RP Selection (P003) to 01 (Feedback pulse) causes the inverter to output the
frequency displayed in the Real Frequency Monitor (d008).
*3. This setting is enabled only when the 1st/2nd Control Method (A044/A244) is set to 03 (Sensorless vector con-
trol). When A044/A244 is not set to 03, the inverter does not produce output because it remains at 0 V.
*4. When the Frequency Conversion Coefficient (b086) is set, the digital output frequency outputs a converted val-
ue. Refer to
7-1-7 Output Frequency Monitor (After Conversion) [d007]
on page 7-6.
PWM output
Pulse output
MP Gain Setting
Parameter
No.
Function name
Data
Default
data
Unit
C105
MP Gain Setting
50. to 200.
Set the MP monitor gain.
100.
%
C030
Digital Current Monitor
Reference Value
0.20
×
Rated current to 2.00
×
Rated current
(In the heavy mode)
0.20
×
Rated current to 1.50
×
Rated current
(In the light mode)
(Set the current value at an output of 1440
Hz.)
Rated
current
A
C047
Pulse Train Output MP
Scale
0.01 to 99.99
Output pulse frequency = Input pulse fre-
quency
×
(C047)
1.00
−
t
T
Cycle T: Constant (6.4 ms)
Duty ratio t/T: Variable
t
T
Cycle T: Variable
Duty ratio t/T: Fixed to 1/2
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...