4 Parameter List
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
4-3 Ext
end
ed F
unc
tion
Mod
e
4
4-
3-1 Gro
up A: S
ta
ndard F
unction Par
ameter
s
*1. This setting is enabled when the Digital Operator with the volume control (Model: 3G3AX-OP01) is connected.
*2. The 3G3MX2-V1 Series Inverter does not provide the high-frequency mode.
*3. These parameters are newly added to the 3G3MX2-V1 Series.
4-3-1
Group A: Standard Function Parameters
Parameter
No.
Function name
Monitor or data range
Default
data
Set
data
Setting
during
RUN
Changes
during
RUN
Unit
Page
Ba
si
c o
peration
se
tting
s
A001
1st Frequency Refer-
ence Selection
00: Digital Operator (Volume)
*1
02
Disabled Disabled
−
P. 5-24
01: Control circuit terminal block
(Analog input)
02: Digital
Operator
(F001)
03: Modbus
communication
A201
2nd Frequency Ref-
erence Selection
04: Option
02
Disabled Disabled
06: Pulse train frequency
07: DriveProgramming
10: Operation
function
output
A002
1st RUN Com-
mand Selection
01: Control terminal block (Drive-
Programming)
02
Disabled Disabled
−
P. 5-22
02: Digital
Operator
A202
2nd RUN Com-
mand Selection
03: Modbus
communication
02
Disabled Disabled
04: Option
A003
1st Base Fre-
quency
30.0 to 1st Maximum Frequency
(A004)
60.0
*2
Disabled Disabled
Hz
P. 5-21
A203
2nd Base Fre-
quency
30.0. to 2nd Maximum Frequency
(A204)
60.0
*2
Disabled Disabled
Hz
A004
1st Maximum Fre-
quency
1st Base Frequency (A003) to 400.0
*2
60.0
*2
Disabled Disabled
Hz
P. 5-21
A204
2nd Maximum Fre-
quency
2nd Base Frequency (A203) to
400.0
*2
60.0
*2
Disabled Disabled
Hz
An
alo
g i
npu
t
A005
FV/FI Selection
00: Switch between FV (Voltage)
and FI (Current)
00
Disabled Disabled
−
P. 7-22
02: Switch between FV (Voltage)
and volume
*1
03: Switch between FI (Current)
and volume
*1
A011
FV Start Frequency
0.00 to 99.99
100.0 to 400.0
*2
0.00
Disabled
Enabled
Hz
P. 7-25
A012
FV End Frequency
0.00 to 99.99
100.0 to 400.0
*2
0.00
Disabled
Enabled
Hz
A013
FV Start Ratio
0. to FV End Ratio
0.
Disabled
Enabled
%
A014
FV End Ratio
FV Start Ratio to 100.
100.
Disabled
Enabled
%
A015
FV Start Selection
00: FV Start Frequency (A011)
01
Disabled
Enabled
−
01: 0
Hz
A016
Analog Input Filter
1. to 30.
31. (500-ms filter with
±
0.1-Hz hys-
teresis)
8.
Disabled
Enabled
−
P. 7-24
Dr
ive
Pr
ogr
ammi
ng
A017
DriveProgramming
Function Selection
*3
00: Disabled
00
Enabled
Enabled
−
P. 7-102
01: Enabled (Start/stop via multi-
function input PRG terminal)
02: Enabled (Start/stop via power
on/off)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...