3 Operation and Test Run
3 - 24
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Precautions for Correct Use
• The following parameters are not initialized: Total RUN Time Monitor (d016), Total Power ON
Time Monitor (d017), Heavy Load/Light Load Selection (b049), Initialization Data Selection
(b085), Initialization Target Setting (b094), FV/FI Adjustment (C081/C082), Thermistor
Adjustment (C085), and Position Data at Power Off (P082).
The DriveProgramming User Parameters U00 to U31 (P100 to P131) are not initialized
unless the Initialization Selection (b084) is set to 04.
• The inverter does not display the initialization-related parameters (b084, b094, b180)
depending on the Display Selection (b037) setting. If they are not displayed, change b037 to
00 (Complete display).
• When the Soft Lock Selection (b031) is set to prohibit changes of the initialization-related
parameters (b084, b094, b180), the initialization cannot be executed. Change the Soft Lock
Selection (b031) to enable the initialization.
• For details on Soft Lock Selection, refer to
7-6-1 Soft Lock Function (SFT)
on page 7-54.
• Remember that you will not be able to revert to the previous settings once you press the
Enter key to execute parameter initialization, with the Initialization Execution (b180) set to 01.
To operate the inverter, two commands are required: the RUN command and the frequency reference.
First, set the sources of these commands in the 1st Frequency Reference Selection (A001) and 1st
RUN Command Selection (A002). For Test Run, set these parameter to 02 (Digital Operator) so as to
operate the inverter via the Digital Operator.
Next, set the 1st Motor Capacity (H003) and the 1st Motor Pole Number (H004). These values will be
used as the reference values for the automatic torque boost, motor protection, and torque limit func-
tions.
Then, in the 1st Electronic Thermal Level (b012), set the rated current of your motor.
Set the value correctly according to the motor.
Precautions for Correct Use
The STOP/RESET key on the Digital Operator is enabled when the STOP Key Selection
parameter is set to Enabled. Make sure that this parameter is set correctly, although the
STOP/RESET key enabled by default.
Parameter Setting
Parameter No.
Function name
Set value
Default data
Unit
A001
1st Frequency Reference
Selection
02: Digital Operator
02
−
A002
1st RUN Command Selec-
tion
02: Digital Operator
02
−
H003
1st Motor Capacity
0.1/0.2/0.4/0.55/0.75/
1.1/1.5/2.2/3.0/3.7/4.0/
5.5/7.5/11.0/15.0/18.5
Maximum applicable
motor capacity
kW
H004
1st Motor Pole Number
2/4/6/8
10 to 48: Do not set.
4
pole
b012
1st Electronic Thermal Level 0.20
×
Rated current to
1.00
×
Rated current
Rated current
A
b087
STOP Key Selection
00: Enabled
00
―
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...