![background image](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918490.webp)
8 Communications Functions
8 - 78
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
144E hex
144D hex
Communication
Parity Selection
C074
R/W
00:
No
−
P. 8-5
01:
Even
02:
Odd
144F hex
144E hex
Communication
Stop Bit Selection
C075
R/W
1:
1 bit
−
2:
2 bits
1450 hex
144F hex
Operation Selection
on Communication
Error
C076
R/W
00:
Trip
−
01:
Trip after decelera-
tion stop
02:
Ignore
03:
Free-run stop
04:
Deceleration stop
1451 hex
1450 hex
Communication
Error Timeout Time
C077
R/W
0:
Timeout disabled
0.01 [s]
1 to 9999
1452 hex
1451 hex
Communication Wait
Time
C078
R/W 0 to 1000
1 [ms]
1453 to
1454 hex
−
Reserved
−
−
−
−
−
1455 hex
1454 hex
FV Adjustment
C081
R/W 0 to 2000
0.1 [%]
P. 7-25
1456 hex
1455 hex
FI Adjustment
C082
R/W 0 to 2000
0.1 [%]
1457 to
1458 hex
−
Reserved
−
−
−
−
−
1459 hex
1458 hex
Thermistor
Adjustment
C085
R/W 0 to 2000
0.1 [%]
P. 7-80
145A to
145E hex
−
Reserved
−
−
−
−
−
145F hex
145E hex
Reserved
C091
R
Do not change the
default 0.
−
−
1460 to
1463 hex
−
Reserved
−
−
−
−
−
1464 hex
1463 hex
Communication
Selection
C096
R/W
00:
Modbus communi-
cation
−
P. 8-31
01:
Co-inverter com-
munication
02:
Co-inverter com-
munication (man-
agement inverter)
1465 hex
−
Reserved
−
−
−
−
−
1466 hex
1465 hex
Co-inverter
Communication
Starting Station
Number
C098
R/W 1 to 8
−
P. 8-31
1467 hex
1466 hex
Co-inverter
Communication
Ending Station
Number
C099
R/W 1 to 8
−
1468 hex
1467 hex
Co-inverter
Communication
Start Selection
C100
R/W
00:
Start via 485 termi-
nal
−
01:
Constant commu-
nication
1469 hex
1468 hex
UP/DWN Storage
Selection
C101
R/W
00:
Not store fre-
quency data
−
P. 7-40
01:
Store frequency
data
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...