6 - 25
6 Vector Control and Applied Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
6-
6 Brake Co
nt
rol Fu
nct
ion
6
6-
6-1 Opera
tion Seq
uence
of Brake Contr
ol F
unction
6-6
Brake Control Function
The 3G3MX2-V1 Series Inverter has a built-in brake control function for an elevating system etc.
Use this function to control the external brake used in an elevating system etc. from the inverter.
The brake control function can be used independently of the 1st/2nd Control Method (A044/A244)
Selection.
In the 3G3MX2-V1 Series, you can combine this function with the simple position control function.
For how to combine this function with simple position control, refer to
6-7-9 Interlock Function with Sim-
ple Position Control and Brake Control
on page 6-49.
This section describes the operation sequence and settings of the brake control function.
Below is the sequence chart for the brake control function, followed by the description of each operation
in the sequence.
Note
The above sequence chart shows an example where one of the Multi-function Input S1 to S7 Selection
(C001 to C007) is set to 44 (BOK: Brake confirmation).
z
During acceleration
(1) When the RUN command turns ON, the inverter starts output and accelerate to the
Brake Release Frequency (b125).
(2) After reaching the Brake Release Frequency, the inverter waits until the Brake
Release Wait Time (b121) elapses and outputs the brake release signal (C021, C022,
C026 = 19: BRK).
However, if the output current does not reach the Brake Release Current (b126) when out-
putting the brake release signal, the inverter outputs the brake error signal (C021, C022,
C026 = 20: BER) without releasing the brake, and detects the E36.
(Brake error).
(3) After outputting the brake release signal, the inverter waits for the brake confirma-
tion signal (C001 to C007 = 44: BOK) to turn ON during the time set in the Brake Error
Detection Time (b124).
If the brake confirmation signal does not turn ON within the time set in b124, the inverter
outputs the brake error signal (C021, C022, C026 = 20: BER) and detects the E36.
(Brake error).
If any of the Multi-function Input S1 to S7 Selection (C001 to C007) is set to 44 (BOK: Brake
confirmation), the Brake Error Detection Time (b124) setting is disabled and the inverter
proceeds to step (4) after outputting the brake release signal.
6-6-1
Operation Sequence of Brake Control Function
(1)
(2)
(5)
(7)
(4)
(3)
(6)
Brake Release Frequency
(b125)
Brake Force Frequency
(b127)
Brake release signal
(BRK output)
Brake confirmation signal
(BOK input)
Stop Wait Time on Brake
Control (b123)
Brake Error Detection Time (b124)
Brake Error Detection Time (b124)
Acceleration Wait Time on
Brake Control (b122)
Brake Release Wait Time (b121)
Output frequency
RUN command
(FW input)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...