8 Communications Functions
8 - 44
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Register
No.
Modbus register
spec. No
Function name
Parameter No.
R/W
Monitor or setting
data
Data
resolution
003A hex
0039 hex
Fault Monitor 5 Fault
Factor
d085
R
Refer to
Inverter trip
fault factor list
on
page 8-46.
−
003B hex
003A hex
Fault Monitor 5 Inverter
Status
Refer to
Inverter trip
fault factor list
on
page 8-46.
−
003C hex
003B hex
Fault Monitor 5 Frequency
(HIGH)
0 to 40000
*1
0.01
[Hz]
003D hex
003C hex
Fault Monitor 5 Frequency
(LOW)
003E hex
003D hex
Fault Monitor 5 Output
Current
Output current
value at the time of
trip
0.01 [A]
003F hex
003E hex
Fault Monitor 5 DC Voltage
DC input voltage at
the time of trip
0.1 [V]
0040 hex
003F hex
Fault Monitor 5 Total RUN
Time (HIGH)
Total RUN time
before the trip
1 [h]
0041 hex
0040 hex
Fault Monitor 5 Total RUN
Time (LOW)
0042 hex
0041 hex
Fault Monitor 5 Total
Power ON Time (HIGH)
Total power ON
time before the trip
1 [h]
0043 hex
0042 hex
Fault Monitor 5 Total
Power ON Time (LOW)
0044 hex
0043 hex
Fault Monitor 6 Fault
Factor
d086
R
Refer to
Inverter trip
fault factor list
on
page 8-46.
−
0045 hex
0044 hex
Fault Monitor 6 Inverter
Status
Refer to
Inverter trip
fault factor list
on
page 8-46.
−
0046 hex
0045 hex
Fault Monitor 6 Frequency
(HIGH)
0 to 40000
*1
0.01
[Hz]
0047 hex
0046 hex
Fault Monitor 6 Frequency
(LOW)
0048 hex
0047 hex
Fault Monitor 6 Output
Current
Output current
value at the time of
trip
0.01 [A]
0049 hex
0048 hex
Fault Monitor 6 DC Voltage
DC input voltage at
the time of trip
0.1 [V]
004A hex
0049 hex
Fault Monitor 6 Total RUN
Time (HIGH)
Total RUN time
before the trip
1 [h]
004B hex
004A hex
Fault Monitor 6 Total RUN
Time (LOW)
004C hex
004B hex
Fault Monitor 6 Total
Power ON Time (HIGH)
Total power ON
time before the trip
1 [h]
004D hex
004C hex
Fault Monitor 6 Total
Power ON Time (LOW)
004E hex
004D hex
Warning Monitor
d090
R
Warning code
−
004F to
08FF hex
−
Not used
−
−
Not accessible
−
*1. The 3G3MX2-V1 Series Inverter does not provide the high-frequency mode.
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...