5 Basic Settings
5 - 42
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
• Enable/disable the STOP/RESET key on the Digital Operator.
• This setting is enabled when the 1st/2nd RUN Command Selection (A002/A202) is not set to 02 (Dig-
ital Operator).
However, when the 1st/2nd RUN Command Selection (A002/A202) is set to 02 (Digital Operator), the
STOP/RESET key is enabled independent of this setting.
Precautions for Safe Use
The STOP/RESET key on the Digital Operator is enabled only when the STOP Key Selection
(b087) is set to 00: Enabled (default data).
Be sure to provide a separate emergency stop switch.
5-7-3
STOP Key Selection
Parameter
No.
Function name
Data
Default
data
Unit
b087
STOP Key Selection
00:
Enabled
00
−
01:
Disabled
02:
Only RESET enabled
Data
STOP command via STOP/RESET key on
Digital Operator
Trip reset via STOP/RESET key on
Digital Operator
00
Enabled
Enabled
01
Disabled
Disabled
02
Disabled
Enabled
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...