5 Basic Settings
5 - 34
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
*1. To enable the switching to the 2nd Acceleration/Deceleration Time 1, set one of the Multi-function Input S1 to
S7 Selection (C001 to C007) to 08 (SET) and turn ON that terminal.
Additional Information
If a short deceleration time is set, the amount of regeneration fed back during deceleration
becomes large. If the amount of regeneration exceeds the amount allowable for the inverter,
the deceleration time will be extended according to the Overvoltage Suppression Function
Selection During Deceleration (b130) setting, or an overvoltage protection (E07.
) is detected.
In such a case, use the regenerative braking function to shorten the deceleration time below
the set value.
For the regenerative braking function
, refer to
5-12-2 Regenerative Braking Function
on page
5-65.
• Use this function to set the acceleration/deceleration pattern for each system.
• Select the acceleration/deceleration pattern in the Acceleration Pattern Selection (A097) and Decel-
eration Pattern Selection (A098).
• The acceleration pattern and the deceleration pattern can be set independently.
• These acceleration/deceleration pattern settings are enabled also for frequency reference input via
analog input terminals.
• When the acceleration/deceleration pattern is set to EL-S-shape curve, do not change the frequency
reference during acceleration/deceleration. Even if the frequency reference is changed during accel-
eration/deceleration, the inverter operates with the EL-S-shape curve before the change, however
the frequency reaches the changed frequency reference.
Parameter
No.
Function name
Data
Default
data
Unit
F002
1st Acceleration Time 1
Acceleration time from 0 to maxi-
mum frequency
0.00 to 99.99
100.0 to 999.9
1000. to 3600.
10.00
s
F202
2nd Acceleration Time 1
*1
F003
1st Deceleration Time 1
Deceleration time from maximum
frequency to 0
0.00 to 99.99
100.0 to 999.9
1000. to 3600.
10.00
s
F203
2nd Deceleration Time 1
*1
P031
Acceleration/Deceleration Time
Input Type
00:
Digital Operator
00
−
03: DriveProgramming
Related functions
A004, A204, C001 to C007
5-6-2
Acceleration/Deceleration Pattern
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...