![Omron SYSDRIVE MX2 SERIES User Manual Download Page 464](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918464.webp)
8 Communications Functions
8 - 52
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolution
Page
1203 hex
1202 hex
1st Base Frequency
A003
R/W
300 to 1st Maximum Fre-
quency
0.1 [Hz]
P. 5-21
1204 hex
1203 hex
1st Maximum
Frequency
A004
R/W
1st Base Frequency to
4000
*1
*1. The 3G3MX2-V1 Series Inverter does not provide the high-frequency mode.
0.1 [Hz]
P. 5-21
1205 hex
1204 hex
FV/FI Selection
A005
R/W
00:
Switch between FV
and FI
−
P. 7-22
02:
Switch between FV
and volume
03:
Switch between FI
and volume
1206 to
120A hex
−
Reserved
−
−
−
−
−
120B hex
120A hex
FV Start Frequency
A011
(HIGH)
R/W 0 to 40000
*1
0.01
[Hz]
*2
*2. When the PID function is enabled, the data unit differs between read and write operations.
Set parameter values in units of 0.01 Hz for writing and in units of 0.1% (as 100% of the maximum frequency)
for reading.
P. 7-25
120C hex
120B hex
A011
(LOW)
120D hex
120C hex
FV End Frequency
A012
(HIGH)
R/W 0 to 40000
*1
0.01
[Hz]
*2
120E hex
120D hex
A012
(LOW)
120F hex
120E hex
FV Start Ratio
A013
R/W 0 to 100
1 [%]
1210 hex
120F hex
FV End Ratio
A014
R/W 0 to 100
1 [%]
1211 hex
1210 hex
FV Start Selection
A015
R/W
00:
FV Start Frequency
(A011)
−
01:
0 Hz
1212 hex
1211 hex
Analog Input Filter
A016
R/W
1 to 30/31 (500-ms filter
with ±0.1-Hz hysteresis)
1
P. 7-24
1213 hex
1212 hex
DriveProgramming
Function Selection
A017
R/W
00:
Disabled
−
−
01:
Enabled (Start/stop
via multi-function
input PRG terminal)
02:
Enabled (Start/stop
at power on/off)
1214 hex
−
Reserved
−
−
−
−
−
1215 hex
1214 hex
Multi-step Speed
Selection
A019
R/W
00:
Binary (16-step selec-
tion with 4 terminals)
−
P. 5-29
01:
Bit (8-step selection
with 7 terminals)
1216 hex
1215 hex
1st Multi-step Speed
Reference 0
A020
(HIGH)
R/W 0
Starting Frequency to 1st
Maximum Frequency
0.01
[Hz]
*2
1217 hex
1216 hex
A020
(LOW)
R/W
1218 hex
1217 hex
Multi-step Speed
Reference 1
A021
(HIGH)
R/W 0
Starting frequency to
Maximum frequency
0.01
[Hz]
*2
1219 hex
1218 hex
A021
(LOW)
R/W
121A hex
1219 hex
Multi-step Speed
Reference 2
A022
(HIGH)
R/W 0
Starting frequency to
Maximum frequency
0.01
[Hz]
*2
121B hex
121A hex
A022
(LOW)
R/W
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...