8 Communications Functions
8 - 26
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Precautions for Correct Use
• The Modbus mapping function settings are reflected on not only Modbus communication, but
also USB communications and communications option units.
Set and use the USB communications and communications option units as follows.
• If the same address is set in the Modbus Mapping External Register 1 to 10 (P201 to P210),
the inverter will return an exception response with the exception code “32 hex” attached to
the communications command.
• If an address that does not exist in the internal Modbus register or double-word data address
is set in the Modbus Mapping Internal Register 1 to 10 (P301 to P310), the inverter will return
an exception response with the exception code “31 hex” or “32 hex” attached to the commu-
nications command.
• Be sure to set the Modbus Mapping External Register Type 1 to 10 (P211 to P220) and Mod-
bus Mapping Scaling 1 to 10 (P221 to P230) correctly. After setting these parameters, check
that data values are set as intended.
Note that the inverter does not perform checks other than the upper and lower limit checks
and operates according to settings even if they are incorrect.
The Modbus mapping function is intended for 16-bit single-word data only and does not support dou-
ble-word data and coils. Therefore, the main information with double-word data is compressed into sin-
gle-word data to be used in the Modbus mapping function. Also, the main coils with single-word data
are provided.
For compressed single-word registers, refer to the list below.
When using CX-Drive: When the CX-Drive is used to read/write parameters, be sure to
set in advance the Modbus Mapping Function Selection (P200) to
00 (Standard Modbus address).
If the Modbus Mapping Function Selection (P200) is set to 01
(Modbus mapping enabled), the operation is performed for the set
address. Therefore the data is not read/written from/to the
intended parameter.
When using communi-
cations option units:
Be sure to set the Modbus Mapping Function Selection (P200) to
00 (Standard Modbus address). Otherwise, the internal process
cannot be performed normally between the inverter and communi-
cations option unit.
8-7-3
Compressed Single-word Registers
Register
No.
Modbus
register
spec. No
Function name
Parameter
No.
R/W
Monitor or setting data
Data
resolu-
tion
1E21 hex
1E20 hex Output Frequency Monitor
d001
R
0 to 40000
0.01
[Hz]
1E22 hex
1E21 hex
PID Feedback Value
Monitor
d004
R
0 to 65535
0.01
1E23 hex
1E22 hex
Output Frequency Monitor
(After conversion)
d007
R
0 to 65535
0.01
1E24 hex
1E23 hex Real Frequency Monitor
d008
R
−
32768 to 32767
0.01
[Hz]
1E25 hex
1E24 hex Fault Monitor 1 Frequency
d081
R
0 to 40000
0.01
[Hz]
1F31 hex
1F30 hex
Output Frequency Setting/
Monitor
F001
R/W
0/Starting frequency to
Maximum frequency
0.01
[Hz]
1F32 hex
1F31 hex 1st Acceleration Time 1
F002
R/W
0 to 65535
0.01 [s]
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...