5 - 59
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-10 Mu
lti-fun
ctio
n
Outpu
t Setting
s
5
5-
10-8 Oper
ation
Ready (IRD
Y)
• This signal is output when the inverter becomes ready to operate (ready to accept the RUN command).
• When this command is not output, the inverter does not operate even if the RUN command is input.
• If this signal is not output, check if the input power supply voltage (R, S, T) is within the specified
range.
• Allocate one of the Multi-function Output P1/P2 Selection (C021/C022), or the Multi-function Relay
Output (MA, MB) Function Selection (C026), to 50 (IRDY).
• This signal is output while the inverter performs the forward operation.
• While the inverter performs the reverse operation or when stopped, this signal is not output.
• Allocate one of the Multi-function Output P1/P2 Selection (C021/C022), or the Multi-function Relay
Output (MA, MB) Function Selection (C026), to 51 (FWR).
• This signal is output while the inverter performs the reverse operation.
• While the inverter performs the forward operation or when stopped, this signal is not output.
• Allocate one of the Multi-function Output P1/P2 Selection (C021/C022), or the Multi-function Relay
Output (MA, MB) Function Selection (C026), to 52 (RVR).
5-10-8 Operation Ready (IRDY)
Parameter
No.
Function name
Data
Default
data
Unit
C021, C022
Multi-function Output P1/P2 Selection
50:
IRDY (Operation
ready)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
05
5-10-9 Forward Run Signal (FWR)
Parameter
No.
Function name
Data
Default
data
Unit
C021, C022
Multi-function Output P1/P2 Selection
51:
FWR (Forward
run signal)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
05
5-10-10 Reverse Run Signal (RVR)
Parameter
No.
Function name
Data
Default
data
Unit
C021, C022
Multi-function Output P1/P2 Selection
52:
RVR (Reverse
run signal)
−
−
C026
Multi-function Relay Output (MA, MB)
Function Selection
05
Output frequency [Hz]
Forward run (FWR) signal
Forward
Reverse
Reverse run (RVR) signal
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...