![Omron SYSDRIVE MX2 SERIES User Manual Download Page 408](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918408.webp)
7 Other Functions
7 - 98
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Perform wiring with reference to
7-10-4 Wiring Example
on page 7-99 to meet the applicable safety
standards. Be sure to use both GS1 and GS2 inputs and configure a system that turns OFF both of the
GS1 and GS2 input signals when the safety function is activated.
If the inverter detects that either the GS1 or GS2 input is OFF, the safety function is activated and the
inverter shuts off the output.
Additional Information
The safety device monitor (62: EDM) turns ON when the inverter detects that both of the GS1
and GS2 input signals turn OFF and shuts off the output. If the EDM output signal does not turn
ON even when the inverter shuts off the output by the safety function, check the GS1 and GS2
input circuits and the EDM detection circuit.
7-10-3 Wiring Safety Function for Use
Parameter
No.
Function name
Data
Default
data
Unit
C003
Multi-function Input S3/S4
Selection
77:
GS1 (GS1 input)
*1
*1. When the safety function selector switch is ON, these functions are forcibly set and cannot be changed.
18
−
C004
78:
GS2 (GS2 input)
*1
12
C013
Multi-function Input S3/S4
Operation Selection
01:
NC (NC contact)
*1
00
−
C014
C021
Multi-function Output P1
Selection
62:
EDM (Safety device monitor)
*2
*2. When the EDM function selector switch is ON, these functions are forcibly set and cannot be changed.
00
−
C031
Multi-function Output P1
Operation Selection
00:
NO (NO contact)
*2
00
−
b145
GS Input Operation Selec-
tion
00:
No trip (shut off by hardware)
00
−
01:
Trip
*3*4
*3. The inverter will trip with E37. If this trip occurs simultaneously with the external trip (E12), the emergency shut-
off (E37) has priority, except at power-on.
*4. The safety function cannot ensure safety if either one of the GS1 and GS2 input terminals turns ON during the
inverter trip with E37.
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...