1 Overview
1 - 12
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
1-3
Specifications
1-3-1
Standard Specifications
3-phase 200-V Class
Item
3-phase 200 V
Model
(3G3MX2-
-V1)
A2001
A2002
A2004
A2007
A2015
A2022
A2037
A2055
A2075
A2110
A2150
Maximum
applicable
motor
capacity
*1
*1. “Applicable motor” represents standard 3-phase motors. When using other types of motors, make sure that the
rated current of the motor does not exceed that of the inverter.
kW
CT
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
VT
0.2
0.4
0.75
1.1
2.2
3.0
5.5
7.5
11
15
18.5
HP
CT
1/8
1/4
1/2
1
2
3
5
7 1/2
10
15
20
VT
1/4
1/2
1
1 1/2
3
4
7 1/2
10
15
20
25
Rated out-
put capac-
ity [kVA]
200 V
CT
0.2
0.5
1.0
1.7
2.7
3.8
6.0
8.6
11.4
16.2
20.7
VT
0.4
0.6
1.2
2.0
3.3
4.1
6.7
10.3
13.8
19.3
23.9
240 V
CT
0.3
0.6
1.2
2.0
3.3
4.5
7.2
10.3
13.7
19.5
24.9
VT
0.4
0.7
1.4
2.4
3.9
4.9
8.1
12.4
16.6
23.2
28.6
Rated input voltage
3-phase 200 V
−
15% to 240 V
+
10%, 50/60 Hz
±
5%
Rated input current
[A]
CT
1.0
1.6
3.3
6.0
9.0
12.7
20.5
30.8
39.6
57.1
62.6
VT
1.2
1.9
3.9
7.2
10.8
13.9
23.0
37.0
48.0
68.0
72.0
Rated output voltage
*2
*2. The output voltage decreases as the input voltage drops.
3-phase 200 to 240 V (Less than incoming voltage)
Rated output current
[A]
CT
1.0
1.6
3.0
5.0
8.0
11.0
17.5
25.0
33.0
47.0
60.0
VT
1.2
1.9
3.5
6.0
9.6
12.0
19.6
30.0
40.0
56.0
69.0
Braking torque during
short-time deceleration
[%]
*3
(discharge resistor not
connected)
*3. The braking torque during capacitor feedback is the average deceleration torque applied when the motor de-
celerates in the shortest deceleration time (when stopped from 50 Hz), not the continuous regenerative torque.
The average deceleration torque varies depending on the motor loss. This value will decrease in operation over
50 Hz.
50
50
50
50
50
20
20
20
20
10
10
Braking
resistor
circuit
*4
*4. The usage rate of the regenerative braking function is 10%.
Regenera-
tive braking
Built-in braking resistor circuit (discharge resistor separately mounted)
Minimum
connection
resistance
[
Ω
]
100
100
100
50
50
35
35
20
17
17
10
Weight [kg]
1.0
1.0
1.1
1.2
1.6
1.8
2.0
3.3
3.4
5.1
7.4
Dimensions (Width
×
Height) [mm]
68
×
128
108
×
128
140
×
128
140
×
260
180
×
296
220
×
350
Dimensions (Depth)
[mm]
109
122.5 145.5
170.5
155
175
CT: Heavy load, VT: Light load
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...