7 Other Functions
7 - 70
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
If a momentary power interruption occur during operation, or if the main circuit DC voltage drops, these
settings will cause the inverter to decelerate with the DC voltage in the main circuit kept at the level set
in the Deceleration Hold Level on Power Interruption (b052).
This function is activated when all of the following start conditions are met:
• b050 = 02 or 03
• During RUN (Disabled during trip, during undervoltage, and during stop)
• The main circuit DC voltage drops to the Starting Voltage on Power Interruption (b051) level or lower.
If the power interruption duration is short, the function allows the inverter to decelerate and stop without
shutting off its output, so the main circuit DC voltage can be kept constant. However, if the power inter-
ruption causes an undervoltage trip, the inverter will shut off its output immediately, so the process of this
function will be terminated. The subsequent operation when the power is restored after a momentary
power interruption depends on the Power Interruption/Undervoltage Restart Selection (b001) setting.
When b050 is set to 03, if the power interruption state is canceled and the incoming voltage is restored before
the occurrence of an under voltage trip, the inverter can recover normal operation. However, this function may
cause deceleration stop depending on the b052 setting. Refer to the table and operation examples below.
If the inverter makes a deceleration stop as a result of this function, it force-terminates the FW (For-
ward) signal even if this signal is ON. To restart the inverter, make sure that the incoming voltage is
recovered and then turn ON the FW (Forward) signal again.
Deceleration Stop on Power Interruption Function: DC Voltage Kept
Constant (b050 = 02: Without Recovery/b050 = 03: With Recovery)
b050
b052
Operation
02 (without recovery)
b052 > Main circuit DC voltage at incoming
voltage recovery
Deceleration stop (DC
voltage constant control)
(Example 1)
b052 < Main circuit DC voltage at incoming
voltage recovery
Deceleration stop (Normal
operation)
(Example 2)
03 (with recovery)
b052 > Main circuit DC voltage at incoming
voltage recovery
Deceleration stop (DC
voltage constant control)
(Example 1)
b052 < Main circuit DC voltage at incoming
voltage recovery
Operation (Normal operation) (Example 2)
VPN [V]
b052
b051
b054
b053
Main circuit P-N voltage
Output frequency
[Hz]
Undervoltage level
Time [s]
Time [s]
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...