5 - 45
5 Basic Settings
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-8 Re
set Met
h
o
d
Sett
ing
s
5
5-
8-2 R
est
a
rt af
ter
Resetting
• In the Reset Restart Selection (C103), select the restart method after trip reset is executed.
However, when the Reset Selection (C102) is set to 03 (Trip reset only), the inverter restarts from 0
Hz independently of the C103 setting.
• To reset via the control circuit terminal block, set the Multi-function Input S1 to S7 Selection (C001 to
C007) to 18 (RS: Reset).
• After the reset signal is input and the motor falls in a free-run state, a large residual voltage remains
between motor terminals.
If the inverter restarts the output in this condition, an overcurrent may occur.
To avoid this, set the Restart Standby Time (b003) to a large value.
• When the Reset Restart Selection (C103) is set to 00 (0-Hz restart), the inverter ignores the Restart
Standby Time (b003) and restarts from 0 Hz.
• Setting Reset Restart Selection (C103) to 01 (Frequency matching restart) causes the inverter to per-
form frequency matching restart also after power cycle.
• The details of the Starting Frequency Selection at Frequency Pull-in Restart (b030) are shown below.
5-8-2
Restart after Resetting
Parameter
No.
Function name
Data
Default
data
Unit
b003
Restart Standby Time
0.3 to 100.0
1.0
s
b007
Frequency Matching Lower
Limit Frequency
0.00 to 99.99
100.0 to 400.0
0.00
Hz
b028
Frequency Pull-in Restart
Level
Heavy
load
(CT)
0.20
×
Rated current to 2.00
×
Rated
current
Rated
current
value
A
Light
load
(VT)
0.20
×
Rated current to 1.50
×
Rated
current
b029
Frequency Pull-in Restart
Parameter
0.1 to 999.9
1000. to 3000.
Set the deceleration rate for the output fre-
quency during frequency pull-in restart.
Set the deceleration time from the maximum fre-
quency to 0 Hz.
0.5
s
b030
Starting Frequency Selec-
tion at Frequency Pull-in
Restart
00:
Frequency at interruption
00
−
01:
Maximum Frequency
02:
Set frequency (Frequency reference)
C103
Reset Restart Selection
00:
0-Hz restart
00
−
01:
Frequency matching restart (Example 1)
02:
Frequency pull-in restart (Example 2)
Set value
Content
Description
00
Frequency at interruption
Executes pull-in restart from frequency at which inverter output is
shut off.
01
Maximum Frequency
Executes pull-in restart from maximum frequency.
02
Set frequency
Executes pull-in restart from set frequency reference.
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...