A-4 UL/cUL Standards Cautions
The warnings and instructions in this section summarizes the procedures necessary to ensure an
inverter installation complies with Underwriters Laboratories guidelines.
• Use 60/75°C Cu wire only.
(For models:3G3MX2-A2001-V1, -A2002-V1, -A2004-V1, -A2007-V1, -AB015-V1, -AB022-V1,
-A4004-V1, -A4007-V1, -A4015-V1, -A4022-V1, and -A4030-V1)
• Use 75°C Cu wire only.
(For models:3G3MX2-AB001-V1, -AB002-V1, -AB004-V1, -AB007-V1, -A2015-V1, -A2022-V1,
-A2037-V1, -A2055-V1, -A2075-V1, -A2110-V1, -A2150-V1, -A4040-V1, -A4055-V1, -A4075-V1,
-A4110-V1 and -A4150-V1)
• Suitable for use on a circuit capable of delivering not more than 100,000 rms Symmetrical Amperes,
240 or 480 Volts Maximum.
• When Protected by CC, G, J, or R Class Fuses, or when Protected By A Circuit Breaker Having An
Interrupting Rating Not Less Than 100,000 rms Symmetrical Amperes, 240 or 480 Volts Maximum.
• Install device in pollution degree 2 environment.
• Maximum surrounding air temperature rating of 50°C
• Solid State motor overload protection reacts with max. 150% of FLA.
• Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the National Electric Code and any additional local
codes.
Terminal Symbols and Screw Size
Model No.
Screw size
Required
torque [N
•
m]
Wire range
3G3MX2-AB001-V1, 3G3MX2-AB002-V1,
3G3MX2-AB004-V1
M3.5
1.0
AWG16 (1.3 mm
2
)
3G3MX2-AB007-V1
M4
1.4
AWG12 (3.3 mm
2
)
3G3MX2-AB015-V1, 3G3MX2-AB022-V1
M4
1.4
AWG10 (5.3 mm
2
)
3G3MX2-A2001-V1, 3G3MX2-A2002-V1,
3G3MX2-A2004-V1, 3G3MX2-A2007-V1
M3.5
1.0
AWG16 (1.3 mm
2
)
3G3MX2-A2015-V1
M4
1.4
AWG14 (2.1 mm
2
)
3G3MX2-A2022-V1
M4
1.4
AWG12 (3.3 mm
2
)
3G3MX2-A2037-V1
M4
1.4
AWG10 (5.3 mm
2
)
3G3MX2-A2055-V1, 3G3MX2-A2075-V1
M5
3.0
AWG6 (13 mm
2
)
3G3MX2-A2110-V1
M6
3.9 to 5.1
AWG4 (21 mm
2
)
3G3MX2-A2150-V1
M8
5.9 to 8.8
AWG2 (34 mm
2
)
3G3MX2-A4004-V1, 3G3MX2-A4007-V1,
3G3MX2-A4015-V1
M4
1.4
AWG16 (1.3 mm
2
)
3G3MX2-A4022-V1, 3G3MX2-A4030-V1
M4
1.4
AWG14 (2.1 mm
2
)
3G3MX2-A4040-V1
M4
1.4
AWG12 (3.3 mm
2
)
3G3MX2-A4055-V1, 3G3MX2-A4075-V1
M5
3.0
AWG10 (5.3 mm
2
)
3G3MX2-A4110-V1, 3G3MX2-A4150-V1
M6
3.9 to 5.1
AWG6 (13 mm
2
)
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...