![Omron SYSDRIVE MX2 SERIES User Manual Download Page 572](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918572.webp)
12 Options
12 - 24
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
• These terminals are used to connect the optional DC reactor for power factor improvement.
By factory setting, a short-circuit bar is connected between the terminals
+
1 and P/
+
2. Before con-
necting the DC reactor, remove this short-circuit bar.
• The length of the DC reactor connection cable must be 5 m or shorter.
• The DC reactor has no polarity.
Precautions for Correct Use
Remove the short-circuit bar only if you connect the DC reactor for use.
If you remove the short-circuit bar with the DC reactor unconnected, the inverter cannot oper-
ate because no power is supplied to its main circuit.
12-5-3 Connection Examples
DC Reactor Connection Terminals (
+
1, P/
+
2)
P/
+
2
M
+
1
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
MC
MCCB
PD
P
3-phase 200 VAC
3-phase 400 VAC
DC reactor
(optional)
Power
supply
Inverter
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...