7 - 63
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-7 R
est
ar
t Fu
nct
ion
s
7
7-7
-2 Rest
art
d
uring Power Int
errup
tion, U
ndervolt
age/Over
-
volt
age, Over
cur
rent
Select whether to have the inverter trip or restart if restart during power interruption, undervoltage/over-
voltage, overcurrent occurs.
Power interruption/Undervoltage restart: When the Power Interruption/Undervoltage Restart Selection
(b001) is set to one of the restart options, the inverter repeats restart operation for the number of times
set in the Power Interruption Restart Count (b005) in the event of a momentary power interruption and
then trips.
Overvoltage/Overcurrent restart: When the Overvoltage/Overcurrent Restart Selection (b008) is set to
one of the restart options, the inverter repeats restart operation for the number of times set in the Over-
voltage/Overcurrent Restart Count (b010) in the event of an undervoltage, and then trips.
Only the Power Interruption Restart Count (b005) can be set to 01 (No limit), which causes the inverter
to trip.
In the Power Interruption/Undervoltage Trip Selection During Stop (b004), select whether or not to have
the inverter trip if a power interruption/undervoltage occurs during stop.
In the Power Interruption/Undervoltage Restart Selection (b001), select the restart condition according to
your system: 0-Hz restart, Frequency matching restart, Trip after frequency matching deceleration stop, or
Frequency pull-in restart.
If the inverter is in an undervoltage state continuously for 40 seconds during restart operation, an
Undervoltage protection (E09) trip will occur.
7-7-2
Restart during Power Interruption, Undervoltage/Overvoltage,
Overcurrent
Restart during Power Interruption, Undervoltage/Overvoltage,
Overcurrent
Parameter
No.
Function name
Data
Description
Default
data
Unit
b001
Power Interruption/Under-
voltage Restart Selec-
tion
*1
*2
00
Trip
00
−
01
0-Hz restart
02
Frequency matching restart
*3
03
Frequency matching restart (Trip
after deceleration stop)
*3
*4
04
Frequency pull-in restart
b002
Allowable Power Interrup-
tion Time
0.3 to 25.0
The inverter restarts if the power
interruption duration is shorter
than the set time. (Example 1)
The inverter trips if the power inter-
ruption duration is equal to or lon-
ger than the set time. (Example 2)
1.0
s
b003
Restart Standby Time
0.3 to 100.
Set the wait time until the inverter
restarts.
1.0
s
b004
Power Interruption/Under-
voltage Trip Selection Dur-
ing Stop
*1
00
Disabled (Trip disabled during
stop)
00
−
01
Enabled (Trip also enabled during
stop)
02
Disabled during stop and during
deceleration by RUN command
OFF.
b005
Power Interruption Restart
Count
00
16 times
00
−
01
No limit
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...