7 - 57
7 Other Functions
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
7-
6 Dig
ita
l Op
erato
r a
nd Op
er
a
tion
Fu
nct
ion
s
7
7-6
-7 Inverte
r Disp
lay on Operat
or Conn
ection
When the inverter is connected with the optional Digital Operator (Model: 3G3AX-OP01), the built-in
Digital Operator keys are disabled. Use this function to set the parameter to display on the built-in Digi-
tal Operator at this time.
Setting the Multi-function Input S1 to S7 Selection (C001 to C007) to 86 (DISP) and turning ON the cor-
responding terminal causes the Digital Operator to display only the content selected in the Initial Screen
Selection (b038), preventing it from displaying other parameters.
Use the password function to set passwords for the Display Selection (b037) and Soft Lock Selection
(b031) functions to prevent display and change of the parameter settings.
Precautions for Correct Use
Be sure not to forget the set password. Note that there is no way to reset the password lock
once you forget the set password and even OMRON factories and service stations have no
means to check your password.
7-6-7
Inverter Display on Operator Connection
Parameter
No.
Function name
Data
Default
data
Unit
b150
Inverter Display on
Operator Connection
001 to 060
Each data corresponds with the monitor mode
parameters d001 to d060.
001
−
7-6-8
Display Fixed (DISP)
Parameter
No.
Function name
Data
Default
data
Unit
C001 to
C007
Multi-function Input S1
to S7 Selection
86:
DISP (Display fixed)
−
−
Related functions
b038
7-6-9
Password Function
Parameter
No.
Function
name
Data
Description
Default
data
Unit
b190
Password A
Setting
0000
Password function disabled.
*1
*1. These passwords cannot be set to 0000.
0000
−
0001 to FFFF
Set the password A for the Display
Selection (b037).
*2
*2. You can use any of the following 16 (hex) characters for parameter setting: 0 to 9, A, b, C, d, E, F.
b191
Password A for
Authentication
0000 to FFFF
Set the password A authentication
parameter.
*2
0000
−
b192
Password B
Setting
0000
Password function disabled.
*1
0000
−
0001 to FFFF
Set the password B for the Soft Lock
Selection (b031).
*2
b193
Password B for
Authentication
0000 to FFFF
Set the password B authentication
parameter.
*2
0000
−
Related functions
b031, b037
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...