![Omron SYSDRIVE MX2 SERIES User Manual Download Page 340](http://html.mh-extra.com/html/omron/sysdrive-mx2-series/sysdrive-mx2-series_user-manual_741918340.webp)
7 Other Functions
7 - 30
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
Adjust the gain and bias settings of the inverter’s AM output based on the meter connected to the termi-
nal AM. The bias setting is once disabled while the reset input is input, and 0 V is output.
AM Gain/Bias Setting
Parameter
No.
Function name
Data
Default
data
Unit
C106
AM Gain Setting
50. to 200.
Set the AM monitor gain.
100.
%
C109
AM Bias Setting
0 to 100
Set the AM monitor bias.
0.
%
(Example) To output 0 to 5 V, set C106 to 50% and use the default data for C109.