5 Basic Settings
5 - 22
Multi-function Compact Inverter 3G3MX2-V1 User’s Manual (I585-E1)
5-4
RUN Command Settings
Select the input method for the RUN command.
Below are the details of the parameter settings.
• If you select 01 (Control circuit terminal block) in the RUN Command Selection, set any two of the
Multi-function Input S1 to S7 Selection (C001 to C007) to 00 (FW: Forward) and 01 (RV: Reverse).
• Also, when using the 3-wire input function, set the RUN Command Selection to 01 (Control circuit ter-
minal block).
For details on the 3-wire input function, refer to
5-9-9 3-wire Input Function (STA, STP, F/R)
on page
5-54.
• When the Multi-function Input S1 to S7 Selection is set to 31 (OPE: Forced operator function) or 51
(F-TM: Forced terminal block), the setting has priority over the 1st/2nd Frequency Reference Selec-
tion (A001/A201) and 1st/2nd RUN Command Selection (A002/A202).
When each terminal is input, the frequency reference and RUN command from the Digital Operator
or the control terminal block are enabled.
• When using the DriveProgramming function to input the RUN command, set the RUN Command
Selection to 01 (Control circuit terminal block).
For details, refer to “DriveProgramming User’s Manual (I580)”.
• To use the Digital Operator to input the RUN command, set the RUN direction in the RUN Direction
Selection (F004).
5-4-1
RUN Command Selection
Parameter
No.
Function name
Data
Default data
Unit
A002/A202
1st/2nd RUN Com-
mand Selection
01:
Control circuit terminal block
(DriveProgramming)
02
−
02:
Digital Operator
03:
Modbus communication
04:
Option
F004
RUN Direction
Selection
00:
Forward
00
−
01:
Reverse
Related functions
F004, C001 to C007
Data
RUN command source
01
Inputs the RUN command via the ON/OFF of the FW/RV signal allocated to the control circuit
terminal block.
It will be regarded as the STOP command if both the forward and reverse commands are input
simultaneously.
02
Inputs the RUN command via the RUN key and the STOP/RESET key on the Digital Operator.
03
Inputs the RUN command via Modbus communication.
04
Inputs the RUN command via the mounted communications option unit.
Summary of Contents for SYSDRIVE MX2 SERIES
Page 1: ...Multi function Compact Inverter MX2 Series Type V1 User s Manual I585 E1 01 3G3MX2 A V1 ...
Page 32: ...CONTENTS 29 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 108: ...2 Design 2 48 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 176: ...4 Parameter List 4 42 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 538: ...10 Troubleshooting 10 22 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 598: ...12 Options 12 50 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 614: ...Appendices A 16 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 ...
Page 615: ...I 1 Multi function Compact Inverter 3G3MX2 V1 User s Manual I585 E1 I Index ...